Omron SYSMAC CV Series Operation Manual page 509

Ladder diagrams
Hide thumbs Also See for SYSMAC CV Series:
Table of Contents

Advertisement

PC Setup Details
Name
F:Execute
Detect low battery
control 1
Error on power off
CPU standby
Measure CPU-bus
Unit (CPU SIOU)
cycle
G:Execute
Execute process
control 2
I/O interrupts
Power OFF interrupt
Dup action process
Step timer
Startup trace
Indirect DM
binary/BCD
(*DM BIN/BCD)
Multiple use of
JMP000
Comparison error
process
Designate whether battery errors are detected. Changes to this setting are
effective immediately.
(Default: Detect)
The following bits will be turned ON when a battery error is detected.
A40204 Battery Low Flag (PC or Memory Card)
A42614 Memory Card Battery Low Flag
A42615 PC Battery Low Flag
Designate whether a momentary power interruption is ignored or treated as a
non-fatal error. If momentary power interrupts are treated as errors, they will be
recorded in the error log (see setting F). Changes to this setting are effective
immediately.
(Default: Not an error)
Designate whether PC operation will begin or the CPU will standby during
initialization and until SYSMAC BUS/2 terminators are properly detected. If this
parameter is set for operation, PC operation will continue even if SYSMAC BUS/2
terminators aren't detected. Changes to this setting are effective immediately.
(Default: CPU standby)
Designate whether or not the time between CPU-bus Unit services is to be
measured. If measured, the cycle is stored starting at A310. Changes to this
setting are effective immediately.
(Default: Don't measure cycle)
Designate whether instruction execution and Peripheral Device servicing are to
be carried out synchronously or asynchronously. If synchronous execution is
used, Peripheral Device access to IOM can be disabled during user program
execution. Changes to this setting are effective the next time the power is turned
ON.
(Default: Asynchronous)
Designate whether or not I/O interrupt program execution is interrupted for
higher-priority I/O interrupts. The I/O interrupt program with the lowest input
number has highest priority.
Power OFF interrupts, power ON interrupts, and scheduled interrupts take priority
over I/O interrupts regardless of this setting.
Changes to this setting are effective immediately.
(Default: Do not interrupt lower-priority I/O interrupts.)
Designate whether or not power OFF interrupts are generated. If an interrupt is
generated, the power OFF interrupt program will be executed. Changes to this
setting are effective immediately.
(Default: No power OFF interrupt)
Not used.
Designate whether the step timer is set in increments of 0.1 s or 1.0 s. Changes
to this setting are effective immediately.
(Default: 0.1 s)
Designate whether a trace is executed automatically according to the preset
conditions when the power is turned on or the operating mode is changed.
Changes to this setting are effective the next time power is turned on.
(Default: Don't start trace.)
Designate whether indirect DM and EM addresses are binary (PC memory
addresses) or BCD (DM and EM area addresses). Changes to this setting are
effective immediately.
(Default: BCD)
Specify whether multiple JMP000 instructions can be programmed. Changes to
this setting are effective immediately.
(Default: Multiple use of JMP000 enabled)
Designate whether or not to start operation even though an I/O verification error
has occurred. This setting affects only the start of PC operation. The I/O
verification error is non-fatal, so PC operation will continue if an I/O verification
error occurs. Changes to this setting are effective immediately.
(Default: Run after error)
Operation
Section 7-2
499