Bit Control Instructions

5-7-5 KEEP: KEEP(011)

Ladder Symbol
S
R
Variations
!KEEP(011)
Description
132
CIO 0005
CIO 0006
CIO 0007
CIO 0010
CIO 0011
CIO 0012
Operand Data Area
(011)
B: Bit
KEEP
B
KEEP(011) is used to maintain the status of the designated bit based on two
execution conditions. These execution conditions are labeled S and R. S is the
set input; R, the reset input. KEEP(011) operates like a latching relay that is set
by S and reset by R.
When S turns ON, the designated bit will go ON and stay ON until reset, regard-
less of whether S stays ON or goes OFF. When R turns ON, the designated bit
will go OFF and stay OFF until reset, regardless of whether R stays ON or goes
OFF. The relationship between execution conditions and KEEP(011) bit status is
shown below.
S execution condition
R execution condition
Status of B
Unchanged
Unchanged
Unchanged