Transition Counter: Tcnt(123) - Omron SYSMAC CV Series Operation Manual

Ladder diagrams
Hide thumbs Also See for SYSMAC CV Series:
Table of Contents

Advertisement

SFC Control Instructions
TN0000
ST0000
0000
TN0000
00
ST0010

5-37-8 TRANSITION COUNTER: TCNT(123)

Ladder Symbol
(123)
TCNT
Description
Precautions
434
If the Transition Flag turns ON, ST0000 is active (but not in pause status), and
ST0010 is inactive, then all of the transition conditions are met and active status
will be transferred from ST0000 to ST0010.
Transition condition
(020)
CMP
D10000
D20000
N
S
When the execution condition is OFF, TCNT(123) is not executed. When the
execution condition is ON, TCNT(123) turns a corresponding Transition Flag
ON or OFF according to the number of times the transition program is executed.
The counter is started the first time TCNT(123) is executed with an ON execution
condition after it is reset and the present value is incremented starting with the
second execution. Therefore, the actual number of execution will be S + 1.
When the present value reaches the value set for S, the Transition Flag and the
Counter Flag will turn ON.
The status of the transition counter is maintained even when step status is
changed, so the transition counter should normally be reset using CNR(236) in
the previous step.
If either TOUT(202) and/or TCNT(123) is used more than once in one transition
program, the status of the Transition Flag will be controlled by the last
TOUT(202) or TCNT(123) in the transition program.
TCNT(123) cannot be used outside of a transition program and writing to the
Transition Flag area cannot be achieved with any instructions other than
TOUT(202) (see previous section) and TCNT(123).
Note
1. A50015 (First Cycle Flag) cannot be used within a transition program.
2. The following three conditions must be met in order for active status to be
transferred from one step to another:
The transition condition (i.e., the Transition Flag) must be ON.
The step(s) before the transition must be active (execute or halt, but not
pause).
The step(s) after the transition must be inactive.
S must be in BCD.
The same counter numbers are used by CNT, CNTR(012), and TCNT(123). Do
not use the same number to define more than one counter, regardless of the
counter instruction used.
The transition counter counts each time the transition program is executed.
When using a parallel join, be particularly careful of the number that is set, be-
cause the transition program will be executed each time the steps just above the
transition are executed.
A500
06(=)
(202)
TOUT
(001)
END
Operand Data Areas
N: Counter number C
S: No. of executions CIO, G, A, T, C, #, DM, DR, IR
Section 5-37
Address Instruction
Operands
00000
LD
000000
00001
CMP(020)
D10000
D20000
00002
AND
A50006
00003
TOUT(202)
00004
END(001)