Omron SYSMAC CV Series Operation Manual page 143

Ladder diagrams
Hide thumbs Also See for SYSMAC CV Series:
Table of Contents

Advertisement

Bit Control Instructions
Precautions
Flags
Example 1
0000
00
(047)
SETA 0005
0000
01
(048)
RSTA 0010
Example 2
0000
00
(047)
SETA 0005 #0008 #0032
0000
01
(048)
RSTA 0010 #0012 #0024
N
must be between 0000 and 0015 and must be BCD. N
1
Note: Refer to page 115 for general precautions on operand data areas.
ER (A50003):
N
N
Content of *DM word is not BCD.
SETA Operation
When CIO 000000 turns ON in the first instruction line in the following example,
eight bits beginning with bit 08 in CIO 0005 are all turned ON.
RSTA Operation
When CIO 000001 turns ON in the second instruction line, the eight bits begin-
ning with bit 12 in CIO 0010 are all turned OFF.
#0008 #0008
#0012 #0004
CIO 0005
CIO 0010
SETA Operation
When CIO 000000 turns ON in the first instruction line in the following example,
32 bits beginning with bit 08 in CIO 0005 are all turned ON.
RSTA Operation
When CIO 000001 turns ON in the second instruction line, 24 bits beginning with
bit 12 in CIO 0010 are all turned OFF.
is not 0000 to 0015 BCD.
1
is not BCD.
2
Unchanged
Section 5-7
must be BCD.
2
Address Instruction
Operands
00000
LD
00001
SETA(047)
00002
LD
00003
RSTA(048)
Unchanged
Address Instruction
Operands
00000
LD
00001
SETA(047)
00002
LD
00003
RSTA(048)
000000
0005
#0008
#0008
000001
0010
#0012
#0004
000000
0005
#0008
#0032
000001
0010
#0012
#0024
131

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cv2000Cvm1Cv500Cv1000

Table of Contents