4. How to program the adjustable frequency
drive
[138]
[139]
[140]
[141]
[142]
[143]
4
[144]
[145]
6-51 Terminal 42 Output Min Scale
Range:
0%
6-52 Terminal 42 Output Max Scale
Range:
100%
92
Torque 4-20 mA
Bus ctrl. 0-20 mA
Bus ctrl. 4-20 mA
Bus ctrl. 0-20 mA,
timeout
Bus ctrl. 4-20 mA,
timeout
Ext. Closed-loop 1,
4-20 mA
Ext. Closed-loop 2,
4-20 mA
Ext. Closed-loop 3,
4-20 mA
*
[0 – 200%]
*
[0.00 – 200%]
MG.20.P1.22 - VLT
VLT AQUA High Power Instruction Manual
Select the function of terminal 42 as an analog current output.
Function:
Scale the minimum output of the selected analog signal at ter-
minal 42, as a percentage of the maximum signal value. For
example, if 0 mA (or 0 Hz) is desired at 25% of the maximum
output value, program it to 25%. Scaling values up to 100% can
never be higher than the corresponding setting in par. 6-52.
Function:
Scale the maximum output of the selected analog signal at ter-
minal 42. Set the value to the maximum value of the current
signal output. Scale the output to give a current lower than 20
mA at full scale; or 20 mA at an output below 100% of the
maximum signal value. If 20 mA is the desired output current
at a value between 0 - 100% of the full-scale output, program
the percentage value in the parameter, i.e., 50% = 20 mA. If a
current between 4 and 20 mA is desired at maximum output
(100%), calculate the percentage value as follows:
m A
desired maximum current
20
/
®
is a registered Danfoss trademark.
× 100 %