4. How to program the adjustable frequency
drive
Activate the AMA function by pressing [Hand on] after selecting [1] or [2]. See also the section
Automatic Motor Adaptation
AMA". After pressing the [OK] key, the adjustable frequency drive is ready for operation.
Note:
4
See section
4.1.3. Function Set-ups
The function set-up provides quick and easy access to all parameters required for the majority of
water and wastewater applications including variable torque, constant torque, pumps, dosing
pumps, well pumps, booster pumps, mixer pumps, aeration blowers and other pump and fan
applications. Among other features, it also includes parameters for selecting which variables to
display on the LCP, digital preset speeds, scaling of analog references, closed-loop single zone
and multi-zone applications and specific functions related to water and wastewater applications.
Example of how to access Function Set-up:
4.2: Step 1: Turn on the adjustable frequency
drive (on LED lights).
76
. After a normal sequence, the display will read: "Press [OK] to finish
For the best adaptation of the adjustable frequency drive, run the AMA on a cold motor.
AMA cannot be performed while the motor is spinning.
NOTE
It is important to set motor par. 1-2* Motor Data correctly, since these form part of
the AMA algorithm. An AMA must be performed to achieve optimum dynamic motor
performance. It may take up to 10 min, depending on the power rating of the motor.
NOTE
Avoid generating external torque during AMA.
NOTE
If one of the settings in par. 1-2* Motor Data is changed, par. 1-30 to 1-39, the
advanced motor parameters, will return to default setting.
This parameter cannot be adjusted while the motor is running.
Automatic Motor Adaptation
MG.20.P1.22 - VLT
VLT AQUA High Power Instruction Manual
- application example.
4.3: Step 2: Press the [Quick Menus] button
(quick menu choices appear).
®
is a registered Danfoss trademark.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT AQUA Drive FC 200 and is the answer not in the manual?

Questions and answers

Table of Contents