VLT AQUA High Power Instruction Manual
6-00 Live Zero Timeout Time
Range:
*
10 s
6-01 Live Zero Timeout Function
Option:
*
[0]
[1]
[2]
[3]
[4]
[5]
Function:
[1 - 99 s]
Enter the Live Zero Timeout time period. Live Zero Timeout
Time is active for analog inputs, (i.e., terminal 53 or terminal
54), allocated to current and used as reference or feedback
sources. If the reference signal value associated with the selec-
ted current input falls below 50% of the value set in par. 6-10,
par. 6-12, par. 6-20 or par. 6-22 for a period of time longer than
that set in par. 6-00, the function selected in par. 6-01 will be
activated.
Function:
Select the timeout function. The function set in par. 6-01 will be
activated if the input signal on terminal 53 or 54 is below 50%
of the value in par. 6-10, par. 6-12, par. 6-20 or par. 6-22 for a
time period defined in par. 6-00. If several timeouts occur si-
multaneously, the adjustable frequency drive prioritizes the
timeout functions as follows:
1.
2.
The output frequency of the adjustable frequency drive can be:
If you select set-up 1-4, par. 0-10,
Multi Set-up
to
This parameter cannot be adjusted while the motor is running.
Off
Freeze output
Stop
Jogging
Max. speed
Stop and trip
®
MG.20.P1.22 - VLT
is a registered Danfoss trademark.
4. How to program the adjustable frequency
Live Zero Timeout Function
Par. 6-01
Par. 8-04
Control Word Timeout Function
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent trip
Active Set-up
, [9].
drive
4
, must be set
89