VLT AQUA High Power Instruction Manual
[1117] XIF Revision
[1118] LON Works Revision
[1501] Running Hours
[1502] kWh Counter
[1600] Control Word
[1601]
[1602] Reference %
[1603] Status Word
[1605] Main Actual Value [%] One or more warnings in a Hex code
[1609] Custom Readout
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Motor Frequency
[1614] Motor Current
[1615] Frequency [%]
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1622] Torque [%]
[1630] DC Link Voltage
[1632] Brake Energy/sec.
[1633] Brake Energy/2 min
Shows the version of the external interface file of the Neuron C
chip on the LON option.
Shows the software version of the application program of the
Neuron C chip on the LON option.
View the number of running hours of the motor.
View the line power consumption in kWh.
View the control word sent from the adjustable frequency drive
via the serial communication port in hex code.
*
Reference [Unit]
Total reference (sum of digital/analog/preset/bus/freeze ref./
catch up and slow-down) in selected unit.
Total reference (sum of digital/analog/preset/bus/freeze ref./
catch up and slow-down) as a percentage.
Present status word
View the user-defined readouts as defined in par. 0-30, 0-31
and 0-32.
Actual power consumed by the motor in kW.
Actual power consumed by the motor in HP.
Voltage supplied to the motor.
Motor frequency, i.e., the output frequency from the adjustable
frequency drive in Hz.
Phase current of the motor measured as effective value.
Motor frequency, i.e., the output frequency from the adjustable
frequency drive as a percentage.
Present motor load as a percentage of the rated motor torque.
Speed in RPM (revolutions per minute), i.e., the motor shaft
speed in closed-loop based on the entered motor nameplate
data, the output frequency and the load on the adjustable fre-
quency drive.
Thermal load on the motor, calculated by the ETR function. See
also parameter group 1-9* Motor Temperature.
Shows the actual torque produced as a percentage.
Intermediate circuit voltage in the adjustable frequency drive.
Present braking energy transferred to an external brake resistor.
Stated as an instantaneous value.
Braking energy transferred to an external brake resistor. The
mean power is calculated continuously for the latest 120 sec-
onds.
®
MG.20.P1.22 - VLT
is a registered Danfoss trademark.
4. How to program the adjustable frequency
drive
4
79