Alarms Generated by the Basic Control Panel

Table 69: Alarms Generated by the Basic Control Panel
The Basic Control Panel indicates Control Panel alarms with a code, A5xxx .
ALARM
CAUSE
CODE
5001
Drive is not responding .
5002
Incompatible communication profile
5010
Corrupted panel parameter backup file
5011
Drive is controlled from another source .
5012
Direction of rotation is locked .
5013
Panel control is disabled because start inhibit is active .
5014
Panel control is disabled because of drive fault .
5015
Panel control is disabled because local control mode lock is active .
5018
Parameter default value is not found .
5019
Writing non-zero parameter value is prohibited .
Parameter or parameter group does not exist or parameter value is
5020
inconsistent .
5021
Parameter or parameter group is hidden .
5022
Parameter is write protected .
5023
Parameter change is not allowed, when drive is running .
5024
Drive is executing task .
5025
Software is being uploaded or downloaded .
5026
Value is at or below minimum limit .
5027
Value is at or above maximum limit .
5028
Invalid value
5029
Memory is not ready .
5030
Invalid request
5031
Drive is not ready for operation, eg due to low DC voltage .
5032
Parameter error
Parameter download error . Selected parameter set is not in current
5040
parameter backup file.
5041
Parameter backup file does not fit into memory.
Parameter download error . Selected parameter set is not in current
5042
parameter backup file.
5043
No start inhibit
5044
Parameter backup file restoring error
5050
Parameter upload aborted
5051
File error
5052
Parameter upload has failed .
5060
Parameter download aborted
5062
Parameter download has failed .
5070
Panel backup memory write error
5071
Panel backup memory read error
5080
Operation is not allowed because drive is not in local control mode .
5081
Operation is not allowed because of active fault .
5083
Operation is not allowed because parameter lock is on .
5084
Operation is not allowed because drive is performing task .
5085
Parameter download from source to destination drive has failed .
5086
Parameter download from source to destination drive has failed .
Parameter download from source to destination drive has failed because
5087
parameter sets are incompatible .
5088
Operation has failed because of drive memory error .
5089
Download has failed because of CRC error .
5090
Download has failed because of data processing error .
5091
Operation has failed because of parameter error .
Parameter download from source to destination drive has failed because
5092
parameter sets are incompatible .
www .DaikinApplied .com
WHAT TO DO
Check panel connection .
Contact your local Daikin representative .
Retry parameter upload . Retry parameter download .
Change drive control to local control mode .
Enable change of direction . See parameter 1003 DIRECTION, page 38 .
Start from the panel is not possible . Reset the emergency stop command
or remove the 3-wire stop command before starting from the panel . See
parameters 1001 EXT1 COMMANDS, 1002 EXT2 COMMANDS and 2109
EMERG STOP SEL .
Reset drive fault and retry .
Deactivate local control mode lock and retry . See parameter 1606 LOCAL
LOCK, page 46 .
Contact your local Daikin representative .
Only parameter reset is allowed .
Contact your local Daikin representative .
Contact your local Daikin representative .
Parameter value is read-only and cannot be changed .
Stop drive and change parameter value .
Wait until task is completed .
Wait until upload/download is complete .
Contact your local Daikin representative .
Contact your local Daikin representative .
Contact your local Daikin representative .
Retry .
Contact your local Daikin representative .
Check input power supply .
Contact your local Daikin representative .
Perform upload function before download .
Contact your local Daikin representative .
Perform upload function before download .
Check that file is compatible with drive.
Retry parameter upload .
Contact your local Daikin representative .
Retry parameter upload .
Retry parameter download .
Retry parameter download .
Contact your local Daikin representative .
Contact your local Daikin representative .
Switch to local control mode .
Check cause of fault and reset fault .
Check parameter 1602 PARAMETER LOCK setting .
Wait until task is completed and retry .
Check that source and destination drive types are same, i .e . ACS320 . See the
type designation label of the drive .
Check that source and destination drive type designations are the same . See
type designation labels of the drives .
Check that source and destination drive information are same . See parameters
in Group 33: Information, page 56 .
Contact your local Daikin representative .
Contact your local Daikin representative .
Contact your local Daikin representative .
Contact your local Daikin representative .
Check that source and destination drive information are same . See parameters
in Group 33: Information, page 56 .
93
f
T
aulT
raCIng
OM 1190-1 • MD4 VFD