Activate Drive Control Functions – EFB

Controlling the Drive

Fieldbus control of various drive functions requires
configuration to:
• Tell the drive to accept fieldbus control of the function.
• Define as a fieldbus input, any drive data required for
control .
• Define as a fieldbus output, any control data required by
the drive .
The following sections describe, at a general level, the
configuration required for each control function. For the
protocol-specific details, see the document supplied with the
FBA module .
Drive Parameter
1001
EXT1 COMMANDS
1002
EXT2 COMMANDS
1003
DIRECTION
1.Daikin MicroTech II controls communicate with the MD4 over Modbus and all parameters are factory set. No field adjustments are recommended.
2 . T he reference provides direction control – a negative reference provides reverse rotation .

Input Reference Select

Using the fieldbus to provide input references to the drive
requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
Table 51: Input Reference Select Protocol Reference
Drive Parameter
1102
EXT1/EXT2 SEL
1103
REF1 SEL
1106
REF2 SEL
Reference Scaling
Where required, REFERENCES can be scaled . See the following, as appropriate:
Daikin MicroTech II controls communicate with the MD4 over
Modbus and all parameters are factory set .
No field adjustments are recommended.
www .DaikinApplied .com
Value
Description
Start/Stop by fieldbus with Ext1
10 (COMM)
selected .
Start/Stop by fieldbus with Ext2
10 (COMM)
selected .
3 (REQUEST)
Direction by fieldbus.
Value
Setting
Reference set selection by
8 (COMM)
fieldbus.
8 (COMM)
Input reference 1 by fieldbus.
8 (COMM)
Input reference 2 by fieldbus.

Start/Stop Direction Control

Using the fieldbus for start/stop/direction control of the drive
requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied command(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
Table 50: Start/Stop Direction Control Protocol Reference
Modbus
abb drv
40001 bits 0...3
40001 bits 0...3
4002/40032
Modbus
abb drv
40001 bit 11
40002
40003
75
f
Ieldbus
Protocol Reference
1
N2
FLN
dcu profile
40031 bits 0, 1
BO1
24
40031 bits 0, 1
BO1
24
40031 bit 3
BO2
22
Protocol Reference
N2
FLN
dcu profile
40031 bit 5
BO5
26
AO1
60
AO2
61
OM 1190-1 • MD4 VFD
C
onTrols
BACnet
BV10
BV10
BV11
BACnet
BV13
AV16
AV17