Programmable Digital Inputs; Programmable Relay Output; Frequency Input - Daikin ACS320 Operation Manual

Wall or cabinet mountable drive for controlling ac motors
Table of Contents

Advertisement

Programmable Digital Inputs

The drive has five programmable digital inputs. The update
time for the digital inputs is 2 ms . It is possible to delay the
state change of digital inputs with delays defined in group
Group 18: FREQ IN & TRAN OUT . This enables very simple
program sequences by connecting several functions with the
same physical wire, eg to remove branches and leaves from a
pipe by running the fan in reverse before normal operation .
One digital input (DI5) can be programmed as a frequency
input . See section "Frequency Input" .
Table 6: Programmable Digital Inputs Settings
Parameter
Group 10: AcStart/Stop/Dir
Group 11: Reference Select
Group 12: Constant Speeds
Group 16: System Controls
Group 18: FREQ IN & TRAN OUT
2109
2201
2209
Table 7: Programmable Digital Inputs Diagnostics
Actual Signal
0160
0414
www .DaikinApplied .com
Additional Information
DI as start, stop, direction
DI in reference selection, or reference
source
DI in constant speed selection
DI as external Run Enable, fault reset
or user macro change signal
DI as external emergency stop
command source
DI as acceleration and deceleration
ramp selection signal
DI as zero ramp force signal
Additional Information
DI status
DI status at the time the latest fault
occurred

Programmable Relay Output

The drive has one programmable relay output . It is possible
to add three additional relay outputs with the optional Relay
Output Extension Module MREL-0 . For more information,
see MREL-01 Relay Output Extension Module User's Manual
(3AUA0000035974 [English]) .
With a parameter setting it is possible to choose what
information to indicate through the relay output: Ready,
running, fault, alarm, etc . The update time for the relay output
is 2 ms .
A value can be written to a relay output through a serial
communication link .
Table 8: Programmable Relay Output Settings
Parameter
Group 14: Relay Outputs
Table 9: Programmable Relay Output Diagnostics
Actual Signal
0134
0162
0173

Frequency Input

Digital input DI5 can be programmed as a frequency input .
Frequency input (0...16000 Hz) can be used as external
reference signal source . The update time for the frequency
input is 50 ms . Update time is shorter when information is
transferred to the application program (50 ms -> 2 ms) .
Table 10: Frequency Input Settings
Parameter
Group 18: FREQ IN & TRAN OUT
1103/1106
4010, 4110, 4210
Table 11: Frequency Input Diagnostics
Actual Signal
0161
25
p
f
rogram
eaTures
Additional Information
RO value selections and operation
times
Additional Information
ROControl Word through fieldbus
control
RO 1 status
RO 2...4 status . With option MREL-
01 only
Additional Information
Frequency input minimum and
maximum values and filtering
External reference REF1/2 through
frequency input
Frequency input as PID reference
source
Additional Information
Frequency input value
OM 1190-1 • MD4 VFD