Bacnet Protocol Technical Data; Binary Input Object Instance Summary; Binary Output Object Instance Summary - Daikin ACS320 Operation Manual

Wall or cabinet mountable drive for controlling ac motors
Table of Contents

Advertisement

BACnet Protocol Technical Data

Binary Input Object Instance Summary

The following table summarizes the Binary Input Objects supported:
Table 61: Binary Input Object Instance Summary
Instance ID
Object Name
Description
BI0
RO 1 ACT
This object indicates the status of Relay Output 1 .
BI1
RO 2 ACT
This object indicates the status of Relay Output 2 (requires MREL-01 option) .
BI2
RO 3 ACT
This object indicates the status of Relay Output 3 (requires MREL-01 option) .
BI3
RO 4 ACT
This object indicates the status of Relay Output 4 (requires MREL-01 option) .
BI6
DI 1 ACT
This object indicates the status of Digital Input 1 .
BI7
DI 2 ACT
This object indicates the status of Digital Input 2 .
BI8
DI 3 ACT
This object indicates the status of Digital Input 3 .
BI9
DI 4 ACT
This object indicates the status of Digital Input 4 .
BI10
DI 5 ACT
This object indicates the status of Digital Input 5 .
NOTE: For Present Value Access Types, R = Read-only,W = Writeable, C = Commandable .
Commandable values support priority arrays & relinquish defaults .

Binary Output Object Instance Summary

The following table summarizes the Binary Output Objects supported:
Table 62: Binary Output Object Instance Summary
Instance ID
Object Name
Description
RO1
This object controls the output state of Relay 1 . This control requires that parameter 1401
BO0
COMMAND
value = COMM .
RO2
This object controls the output state of Relay 2 . This control requires that parameter 1402
BO1
COMMAND
value = COMM (also requires MREL-01 option) .
RO3
This object controls the output state of Relay 3 . This control requires that parameter 1403
BO2
COMMAND
value = COMM (also requires MREL-01 option) .
RO4
This object controls the output state of Relay 4 . This control requires that parameter 1410
BO3
COMMAND
value = COMM (also requires MREL-01 option) .
NOTE: For Present Value Access Types, R = Read-only,W = Writeable, C = Commandable .
Commandable values support priority arrays & relinquish defaults .
www .DaikinApplied .com
83
f
C
Ieldbus
onTrols
Present Value
Active/Inactive Text
Access Type
ON/OFF
R
ON/OFF
R
ON/OFF
R
ON/OFF
R
ON/OFF
R
ON/OFF
R
ON/OFF
R
ON/OFF
R
ON/OFF
R
Present Value
Active/Inactive Text
Access Type
ON/OFF
C
ON/OFF
C
ON/OFF
C
ON/OFF
C
OM 1190-1 • MD4 VFD