MD4 Self-contained SAF
Figure 31: MD4 RoofPak and Self-Contained Air Conditioner Supply Air Fan
25 A+
24 B-
+NB
VFD10
SAF
SCR
AI1
MD4
AGND
B
L
10V
A J
C
AI2
K
AGND
AO1
J
AGND
24V
GND 10
J
DCOM 11 Jumper to establish digital ground reference
DI1 12
C63
DI2 13 DHL
DI3 14
BUS
TERMINAL *
DI4 15
DI5 16
JUMPERS**
RO1C 17
ma
ma
RO1A 18
RO1B 19
V
V
AI1
AI2
OM 1190-1 • MD4 VFD
WHITE
BLACK
8
RJ-
REMOTE KEYPAD CONNECTION
45
X1A
1
SHIELD OF ALL SIGNAL CABLES
2
WHT
3
BLK
4
DRN
5
WHT
6
BLK
7
8
9
YELLOW
to internal 24VDC supply.
Run Enable
XIB
A+1/2.12
B-1/2.13
+NB
SPS1
DUCT
TB1(-)
STATIC
PRESSURE
TB1(+)
+NB
SPS-X
TB1(-)
TB1(+)
MB
R63
9
5
* Top pins jumpered to the Modbus "terminated" position
** Top 2 pins jumpered to the milliamp position