Daikin ACS320 Operation Manual page 43

Wall or cabinet mountable drive for controlling ac motors
Table of Contents

Advertisement

Code
Description (continuation of Table 28)
-1 = DI1(INV) – Selects Constant Speed 1 with digital input DI1 .
• Inverse operation: Digital input de-activated = Constant Speed 1 activated .
-2...- 5 = DI2(INV)...DI5(INV) – Selects Constant Speed 1 with digital input . See previous .
-7 = DI1,2(INV) – Selects one of three Constant Speeds (1...3) using DI1 and DI2 .
• Inverse operation uses two digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
DI1 DI2
Function
1
1
No constant speed
0
1
Constant speed 1 (1202)
1
0
Constant speed 2 (1203)
0
0
Constant speed 3 (1204)
-8 = DI2,3(INV) – Selects one of three Constant Speeds (1...3) using Di2 and DI3 .
• See above (DI1,2(INV)) for code .
-9 = DI3,4(INV) – Selects one of three Constant Speeds (1...3) using DI3 and DI4 .
• See above (DI1,2(INV)) for code .
-10 = DI4,5(INV) – Selects one of three Constant Speeds (1...3) using DI4 and DI5 .
• See above (DI1,2(INV)) for code .
-12 = DI1,2,3(INV) – Selects one of seven Constant Speeds (1 . . .7) using DI1, DI2 and DI3 .
DI1 DI2 DI3
Function
1
1
1
No constant speed
0
1
1
Constant speed 1 (1202)
1
0
1
Constant speed 2 (1203)
0
0
1
Constant speed 3 (1204)
1
1
0
Constant speed 4 (1205)
0
1
0
Constant speed 5 (1206)
1
0
0
Constant speed 6 (1207)
0
0
0
Constant speed 7 (1208)
• Inverse operation uses three digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
-13 = DI3,4,5(INV) – Selects one of seven Constant Speeds (1...3) using DI3, DI4 and DI5 .
• See above (DI1,2,3(INV)) for code .
www .DaikinApplied .com
43
a
s
p
CTual
Ignals and
arameTers
Range
Resolution
Default
OM 1190-1 • MD4 VFD