(continuation of Table 70)
CODE
FAULT
SERF CORRUPT (FF55)
0101
0307 bit 14
0103
SERF MACRO (FF55) 0307 bit 14
DSP T1 OVERLOAD (6100)
0201
0307 bit 13
DSP T2 OVERLOAD (6100)
0202
0307 bit 13
DSP T3 OVERLOAD (6100)
0203
0307 bit 13
DSP STACK ERROR (6100)
0204
0307 bit 12
0206
CB ID ERROR (5000) 0307 bit 11
1000
PAR HZRPM (6320) 0307 bit 15
PAR PFC REF NEG (6320)
1001
0307 bit 15
1003
PAR AI SCALE (6320) 0307 bit 15
1004
PAR AO SCALE (6320) 0307 bit 15
1005
PAR PCU 2 (6320) 0307 bit 15
1006
PAR EXT RO (6320) 0307 bit 15
1007
PAR FBUSMISS (6320) 0307 bit 15
1009
PAR PCU 1 (6320) 0307 bit 15
1012
PAR PFC IO 1 (6320) 0307 bit 15
1013
PAR PFC IO 2 (6320) 0307 bit 15
1014
PAR PFC IO 3 (6320) 0307 bit 15
OM 1190-1 • MD4 VFD
CAUSE
Drive internal error
Incorrect frequency limit parameter
setting
Incorrect PFC parameters
Incorrect analog input AI signal
scaling
Incorrect analog output AO signal
scaling
Incorrect motor nominal power
setting
Incorrect extension relay output
parameters .
Fieldbus control has not been
activated .
Incorrect motor nominal speed/
frequency setting
I/O configuration for PFC not
complete
I/O configuration for PFC not
complete
I/O configuration for PFC not
complete .
The drive is unable to allocate a
digital input (interlock) for each PFC
motor .
96
WHAT TO DO
Write down fault code and contact your local Daikin representative .
Check parameter settings .
Check that following applies:
• 2007 MINIMUM FREQ < 2008 MAXIMUM FREQ • 2007 MINIMUM FREQ /
9907 MOTOR NOM FREQ and 2008 MAXIMUM FREQ / 9907 MOTOR NOM
FREQ are within range .
Check parameter Group 81: PFA settings .
Check that following applies:
• 2007 MINIMUM FREQ > 0 when 8123 is ACTIVE or SPFC ACTIVE .
Check parameter Group 13: Analog Inputs settings .
Check that following applies:
• 1301 MINIMUM AI1 < 1302 MAXIMUM AI1
• 1304 MINIMUM AI2 < 1305 MAXIMUM AI2 .
Check parameter Group 15: Analog Outputs settings .
Check that following applies:
• 1504 MINIMUM AO1 < 1505 MAXIMUM AO1 .
Check parameter 9009 setting .
Following must apply:
• 1 .1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1 .73 / PN)
< 3 .0 where PN = 1000 * 9909 MOTOR NOM POWER (if units are in kW)
or PN = 746 * 9909 MOTOR NOM POWER (if units are in hp) .
Check parameter settings .
Check that following applies:
• Relay Output Extension Module MREL-0 is connected to the drive .
• 1402...1403 RELAY OUTPUT 2...3 and 1410 RELAY OUTPUT 4 have
non-zero values . See MREL-01 Relay Output Extension Module
User's Manual (3AUA0000035974 [English]) .
Check fieldbus parameter settings.
Check parameter settings .
Following must apply:
• 1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED) < 16
• 0 .8 < 9908 MOTOR NOM SPEED / (120 * 9907 MOTOR NOM FREQ /
Motor poles) < 0 .992
Check parameter settings .
Following must apply:
• There are enough relays parameterized for PFC .
• No conflict exists between parameter Group 14: Relay Outputs, parameter
8117 NR OF AUX MOT and parameter 8118 AUTOCHNG INTERV .
Check parameter settings .
Following must apply:
• The actual number of PFC motors (parameter 8127 MOTORS) matches
the PFC motors in parameter Group 14: Relay Outputs and parameter
8118 AUTOCHNG INTERV .
See parameters 8120 INTERLOCKS and 8127 MOTORS, page 93 .
f
T
aulT
raCIng
www .DaikinApplied .com