Parameters Mode
Figure 11: Changing in the Parameters
To change the parameters, follow these steps:
1
Select the Parameters mode with the UP/DOWN buttons and
2
select ENTER to select the Parameters mode .
Select the appropriate parameter group with
3
the UP/DOWN buttons and select SEL
Select the appropriate parameter in a group
4
Select EDIT to change the parameter value .
Press the UP/DOWN buttons to change the parameter value .
5
Select SAVE to store the modified value or select CANCEL to leave the set
mode .
6
• Any modifications not saved are cancelled.
• Each individual parameter setting is valid immediately after pressing SAVE .
Select EXIT to return to the listing of parameter groups,
7
To complete the control connections by manually entering the parameters, see Parameters Mode above .
For detailed hardware description, see the
NOTE: The current parameter value appears below the
highlighted parameter .
To view the default parameter value, press the UP/
DOWN buttons simultaneously .
The most typical and necessary parameters to
change are parameter groups 99 Start-up data, 10
Start/Stop/Dir, 11 Reference Select, 20 Limits, 21
Start/Stop, 22 Accel/Decel, 30 Fault Functions and
98 & 53 Groups for Comms .
To restore the default factory settings, select the
application macro HVAC default .
OM 1190-1 • MD4 VFD
Select MENU to enter the main menu .
with the UP/DOWN buttons .
and again to return to the main menu .
"Technical Data" starting on page 102
.
16