Daikin ACS320 Operation Manual page 34

Wall or cabinet mountable drive for controlling ac motors
Table of Contents

Advertisement

Code
Description (continuation of Table 23)
0132
PID 1 DEVIATION
The difference between the PID 1 controller reference value and actual value .
• Units and scale defined by PID parameters 4006/4106 & 4007/4107.
0133
PID 2 DEVIATION
The difference between the PID 2 controller reference value and actual value .
• Units and scale defined by PID parameters 4206 & 4207.
0134
COMM RO WORD
Free data location that can be written from serial link .
• Used for relay output control .
• See parameter 1401 .
0135
COMM VALUE 1
Free data location that can be written from serial link .
0136
COMM VALUE 2
Free data location that can be written from serial link .
0137
PROCESS VAR 1
Process variable 1
• Defined by parameters in Group 34: Panel Display / Process Variables,
0138
PROCESS VAR 2
Process variable 2
• Defined by parameters in Group 34: Panel Display / Process Variables,
0139
PROCESS VAR 3
Process variable 3
• Defined by parameters in Group 34: Panel Display / Process Variables,
0140
RUN TIME
The drive's accumulated running time in thousands of hours (kh) .
0141
MWH COUNTER
The drive's accumulated power consumption in megawatt hours . Cannot be reset .
0142
REVOLUTION CNTR
The motor's accumulated revolutions in millions of revolutions .
0143
DRIVE ON TIME (HI)
The drive's accumulated power on time in days .
0144
DRIVE ON TIME (LO)
The drive's accumulated power on time in 2 second ticks (30 ticks = 60 seconds) .
0145
MOTOR TEMP
Motor temperature in degrees centigrade / PTC rdsistance in Ohms .
• Applies only if motor temperature sensor is set up . See parameter 3501,
0158
PID COMM VALUE 1
Data received from fieldbus for PID control (PID1 and PID2).
0159
PID COMM VALUE 2
Data received from fieldbus for PID control (PID1 and PID2).
0160
DI 1-5 STATUS
Status of digital inputs .
EXAMPLE: 10000 = DI1 is on, DI2 . . .DI5 are off .
0161
PULSE INPUT FREQ
Value of frequency input in Hz .
0162
RO STATUS
Status of relay output 1 .1 = RO is energized, 0 = RO is deenergized .
0163
TO STATUS
Status of transistor output when transistor output is used as a digital output .
0164
TO FREQUENCY
Transistor output frequency, when transistor output is used as a frequency output .
0173
RO 2-4 STATUS
Status of the relays in the Relay Output Extension Module MREL-0 . See MREL-01 Relay Output Extension Module User's Manual (3AUA0000035974 [English]) .
Example: 100 = RO 2 is on, RO3 and RO 4 are off .
0174
SAVED KWH
Energy saved in kWh compared to the energy used when the pump is connected directly to the supply . Can be reset with parameter 4509 ENERGY RESET (resets all energy
calculators at the same time) . See Group 45 ENERGY SAVING,
0175
SAVED MWH
Energy saved in MWh compared to the energy used when the pump is connected directly to the supply . Can be reset with parameter 4509 ENERGY RESET (resets all energy
calculators at the same time) . See Group 45 ENERGY SAVING,
0176
SAVED AMOUNT 1
Energy saved in local currency. To find out the total saved energy in currency units, add the value of parameter 0177 multiplied by 1000 to the value for parameter 0176.
Example:
0176 SAVED AMOUNT 1 = 123 .4
0177 SAVED AMOUNT 2 = 5
Total saved energy = 5 * 1000 + 123 .4 = 5123 .4 currency units . Local energy price is set with parameter 4502 ENERGY PRICE . Can be reset with parameter 4509 ENERGY RESET
(resets all energy calculators at the same time) .
See Group 45 ENERGY SAVING,
OM 1190-1 • MD4 VFD
page
page
page
page
page
66 .
page
66 .
page
66 .
57 .
57 .
57 .
59 .
34
a
s
p
CTual
Ignals and
arameTers
Range
Resolution
Default
0 . . .65535
1
0
-32768 . . .
1
+32767
-32768 . . .
1
0
+32767
1
1
1
0 . . .499 .99 kh
0 .01 kh
0 kh
0 . . .65,535
1 MWh
MWh
0 . . .9999
1
0
0 . . .65535 days
1 day
0
0 . . .43200
2s
0
hh:mm:ss
-10 . . .200 °C/
0 . . .5000 Ohm /
1
0
0 . . .1
1 = 1 Hz
1 = 1
1 = 1
1 = 1 Hz
1 = 0 .1 kWh
1 = 1 MWh
1 = 0 .1
(Currency)
www .DaikinApplied .com