Group 03: Actual Signals - Daikin ACS320 Operation Manual

Wall or cabinet mountable drive for controlling ac motors
Table of Contents

Advertisement

Code
Description (continuation of Table 23)
0177
SAVED AMOUNT 2
Energy saved in local currency in thousand currency units . Eg value 5 means 5000 currency units . See parameter 0176 SAVED AMOUNT 1 .
Local energy price is set with parameter 4502 ENERGY PRICE . Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time) .
See Group 45 ENERGY SAVING,
0178
SAVED CO
2
Reduction on carbon dioxide emissions in tn . CO
(resets all energy calculators at the same time) . See Group 45 ENERGY SAVING,

Group 03: Actual Signals

This group monitors fieldbus communications.
Table 24: Group 03: Actual Signals
Code
Description
0301
FB CMD WORD 1
Read-only copy of the Fieldbus Command Word 1 .
• The fieldbus command is the principal means for controlling the drive from a fieldbus controller. The command consists of two Command Words. Bit-coded instructions in the
Command Words switch the drive between states .
• To control the drive, using the Command Words, an external location (EXT1 or EXT2) must be active and set to COMM . (See parameters 1001 and 1002 .)
• The control panel displays the word in hex . For example, all zeros and a 1 in Bit 0 displays as 0001 . All zeros and a 1 in BIt 15 displays as 8000 .
Bit #
0301, fb cmd word 1
0
STOP
1
START
2
REVERSE
3
LOCAL
4
RESET
5
EXT2
6
RUN_DISABLE
7
STPMODE_R
0302
FB CMD WORD 2
Read-only copy of the Fieldbus Command Word 2 .
• See parameter 0301,
page
35 .
0303
FB STS WORD 1
Read-only copy of the Status Word 1 .
• The drive sends status information to the fieldbus controller. The status consists of two Status Words.
Bit #
0303, sts cmd word 1 0304, fb sts word 2
0
READY
1
ENABLED
2
STARTED
3
RUNNING
4
ZERO_SPEED
5
ACCELERATE
6
DECELERATE
7
AT_SETPOINT
0304
FB STS WORD 2
Read-only copy of the Status Word 2 .
• See parameter 0303,
page
35 .
0305
FAULT WORD 1
Read-only copy of the Fault Word 1 .
• When a fault is active, the corresponding bit for the active fault is set in the Fault Words .
• Each fault has a dedicated bit allocated within Fault Words .
• See Fault Tracing,
page 90
for a description of the faults .
The control panel displays the word in hex . For example, all zeros and a 1 in Bit 0 displays a 0001 . All zeros and a 1 in Bit 15 displays as 8000 .
Bit #
0305,fault word 1
0
OVERCURRENT
1
DC OVERVOLT
2
DEV OVERTEMP
3
SHORT CIRC
4
Reserved
5
DC UNDERVOLT
6
AI1 LOSS
7
AI2 LOSS
0306
FAULT WORD 2
A16-bit data word. For the possible causes and remedies and fieldbus equivalents, see Fault Tracing,
Bit #
0
Reserved
1
THERM FAIL
2 . . .3 Reserved
4
CURR MEAS
5
SUPPLY PHASE
www .DaikinApplied .com
page
66 .
conversion factor is set with parameter 4507 CO
2
0302, fb cmd word 2
Bit #
0301, fb cmd word 1
FBLOCAL_CTL
8
STPMODE_EM
FBLOCAL_REF
9
STPMODE_C
START_DISABLE1
10
RAMP_2
START_DISABLE2
11
RAMP_OUT_0
Reserved
12
RAMP_HOLD
Reserved
13
RAMP_IN_0
Reserved
14
RREQ_LOCALLOC
Reserved
15
TORQLIM2
Bit #
0303, sts cmd word 1
ALARM
8
LIMIT
REQ_MAINT
9
SUPERVISION
DIRLOCK
10
REV_REF
LOCALLOCK
11
REV_ACT
CTL_MODE
12
PANEL_LOCAL
Reserved
13
FIELDBUS_LOCAL
Reserved
14
EXT2_ACT
Reserved
15
FAULT ACK_
0306 fault word 2
0307 fault word 3
UNDERLOAD
EFB 1
THERM FAIL
EFB 2
OPEX LINK
EFB 3
OPEX PWR
Incompatible software type
CURR MEAS
Reserved
SUPPLY PHASE
Reserved
ENCODER ERROR
Reserved
OVERSPEED
Reserved
Bit #
6
Reserved
7
OVERSPEED
8
Reserved
9
DRIVE ID
10
CONFIG FILE
CONV FACTOR . Can be reset with parameter 4509 ENERGY RESET
2
page
66 .
0302, fb cmd word 2
Reserved
Reserved
Reserved
REF_CONST
REF_AVE
LINK_ON
REQ_STARTINH
OFF_INTERLOCK
0304, fb sts word 2
Reserved
Reserved
REQ_CTL
REQ_REF1
REQ_REF2
REQ_REF2EXT
ACK_STARTINH
OFF_ILCK
Bit #
0305, fault word 1
0306, fault word 2
8
MOT OVERTEMP
Reserved
9
PANEL LOSS
DRIVE ID
10
ID RUN FAIL
CONFIG FILE
11
MOTOR STALL
SERIAL 1 ERR
12
Reserved
EFB CON FILE
13
EXT FLT 1
FORCE TRIP
14
EXT FLT 2
MOTOR PHASE
15
EARTH FAULT
OUTPUT WIRING
page
90 .
Bit #
11
SERIAL 1 ERR
12
EFB CON FILE
13
FORCE TRIP
14
MOTOR PHASE
15
OUTP WIRING
35
a
s
p
CTual
Ignals and
arameTers
Range
Resolution
Default
1 = 1000
(Currency)
1 = 0 .1 tn
Range
Resolution
Default
1
- hex
1
- hex
1
0000 hex
0307, fault word 3
Reserved
Reserved
System Error
System Error
System Error
System Error
Hardware Error
Param . Setting Fault
-
1
0000 hex
OM 1190-1 • MD4 VFD
S
S