Daikin ACS320 Operation Manual page 64

Wall or cabinet mountable drive for controlling ac motors
Table of Contents

Advertisement

Code Description (continuation of Table 43)
4007
UNIT SCALE
Defines the decimal point location in PID controller actual values.
4007 Value
Entry
Display
0
0003
1
0031
2
0314
3
3142
• Enter the decimal point location counting in from the right of the entry .
• See table for example using pi (3 .14159) .
4008
0 % VALUE
Defines (together with the next parameter) the scaling applied to the PID controller's actual values
(PID1 parameters 0128, 0130, and 0132) .
• Units and scale are defined by parameters 4006 and 4007.
4009
100 % VALUE
Defines (together with the previous parameter) the scaling applied to the PID controller's actual values.
• Units and scale are defined by parameters 4006 and 4007.
4010
SET POINT SEL
Defines the reference signal source for the PID controller.
• Parameter has no significance when the PID regulator is by-passed (see 8121 REG BYPASS CTRL).
0 = KEYPAD – Control panel provides reference .
1 = AI1 – Analog input 1 provides reference .
2 = AI2 – Analog input 2 provides reference .
8 = COMM – Fieldbus provides reference .
9 = COMM + AI1 – Defines a fieldbus and analog input 1 (AI1) combination as the reference source. See Analog Input Reference Correction below.
10 = COMM * AI1 – Defines a fieldbus and analog input 1 (AI1) combination as the reference source. See Analog Input Reference Correction below.
11 = DI3U, 4D(RNC) – Digital inputs, acting as a motor potentiometer control, provide reference .
• DI3 increases the speed (the U stands for "up")
• DI4 decreases the reference (the D stands for "down") .
• Parameter 2205 ACCELER TIME 2 controls the reference signal's rate of change .
• R = Stop command resets the reference to zero .
• NC = Reference value is not copied .
12 = DI3U, 4D(NC) – Same as DI3U, 4D(RNC) above, except:
• Stop command does not reset reference to zero . At restart the motor ramps up, at the selected acceleration rate, to the stored reference .
13 = DI5U, 6D(NC) – Same as DI3U, 4D(NC) above, except:
• Uses digital inputs DI5 and DI6 .
14 = AI1 + AI2 – Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See Analog Input Reference Correction below.
15 = AI1 * AI2 – Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See Analog Input Reference Correction below.
16 = AI1 - AI2 – Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See Analog Input Reference Correction below.
17 = AI1/AI2 – Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See Analog Input Reference Correction below.
19 = INTERNAL – A constant value set using parameter 4011 provides reference .
Analog Input Reference Correction
Parameter values 9, 10, and 14...17 use the formula in the following table .
Value Setting
AI reference is calculated as following:
C + B
C value + (B value - 50% of reference value)
C * B
C value * (B value / 50% of reference value)
C - B
(C value + 50% of reference value) - B value
C / B
(C value * 50% of reference value) / B value
Where:
• C = Main Reference value ( = COMM for values 9, 10 and = AI1 for values 14...17) .
• B = Correcting reference ( = AI1 for values 9, 10 and = AI2 for values 14...17) .
Example: The figure shows the reference source curves for value settings 9, 10, and 14...17, where:
• C = 25% .
• P 4012 SETPOINT MIN = 0 .
• P 4013 SETPOINT MAX = 0 .
• B varies along the horizontal axis .
20 = PID2OUT – Defines PID controller 2 output (parameter 0127 PID 2 OUTPUT) as the reference source.
OM 1190-1 • MD4 VFD
3
3 .1
3 .14
3 .142
a
64
s
p
CTual
Ignals and
arameTers
Range
Resolution
Default
0...4
1
1
-1000 .0...
0 .1%
0 .0%
1000 .0%
-1000 .0...
0 .1%
100%
1000 .0%
0 . . .19
1
0
www .DaikinApplied .com
S

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Md 4

Table of Contents