Modes - Daikin ACS320 Operation Manual

Wall or cabinet mountable drive for controlling ac motors
Table of Contents

Advertisement

NOTE: The current parameter value appears below the
highlighted parameter .
To view the default parameter value, press the UP/
DOWN buttons simultaneously .
The most typical and necessary parameters to
change are parameter groups 99 Start-up data, 10
Start/Stop/Dir, 11 Reference Select, 20 Limits, 21
Start/Stop, 22 Accel/Decel, 30 Fault Functions and
98 & 53 Groups for Comms .
To restore the default factory settings, select the
application macro HVAC default .

Modes

The MD4 HVAC control panel has several different modes for
configuring, operating and diagnosing the drive. The modes are:
• Standard display mode – Shows drive status information
and operates the drive .
• Parameters mode – Edits parameter values individually .
• Changed parameters mode – Shows changed
parameters .
• Fault logger mode – Shows the drive fault history .
• Drive parameter backup mode – Stores or uploads the
parameters .
• Clock set mode – Sets the time and date for the drive .
• Alarm mode – Reporting mode triggered by drive alarms .
OM 1190-1 • MD4 VFD
Standard Display Mode
Use the standard display mode to read information on the
drive's status and to operate the drive . To reach the standard
display mode, press EXIT until the LCD display shows status
information as described below .
Status Information
Table 1: Status Information
Control Panel Display
Rotating arrow (clockwise or
counterclockwise)
Rotating dotted arrow blinking
Stationary dotted arrow
Top . The top line of the LCD display shows the basic status
information of the drive .
• Hand – Indicates that the drive control is local, that is,
from the control panel .
• Auto – Indicates that the drive control is remote, such as
the basic I/O (X1) or fieldbus.
– Indicates the drive and motor rotation status as
follows:
Upper Right – shows the active reference .
Middle . Using parameter group 34 on
of the LCD display can be configured to display:
• One to three parameter values
— The default display shows
parameters 0103 (OUTPUT
FREQ) in percentages,
0104 (CURRENT) in
amperes and 0120 (AI1) in
milliamperes .
— Use parameters 3401, 3408, and 3415 to select the
parameters (from Group 01) to display . Entering
"parameter" 0100 results in no parameter displayed .
For example, if 3401 = 0100 and 3415 = 0100, then
only the parameter specified by 3408 appears in the
Control Panel display .
— You can also scale each parameter in the display, for
example, to convert the motor speed to a display of
conveyor speed . Parameters 3402...3405 scale the
parameter specified by 3401, parameters 3409...3412
scale the parameter specified by 3408, etc.
• A bar meter rather than one of the parameter values .
— Enable bar graph displays using parameters 3404,
3411 and 3418 .
Bottom . The bottom of the LCD display shows:
• Lower Corners – show the functions currently assigned
to the two soft keys .
• Lower Middle – displays the current time (if configured to
show the time) .
14
s
TarT
Significance
• Drive is running and at setpoint
• Shaft direction is forward or reverse
Drive is running but not at setpoint
Start command is present, but motor
is not running . E .g . start enable is
missing .