Binary Valueobject Instance Summary - Daikin ACS320 Operation Manual

Wall or cabinet mountable drive for controlling ac motors
Table of Contents

Advertisement

Binary ValueObject Instance Summary

The following table summarizes the Binary Output Objects supported:
Table 63: Binary Value Object Instance Summary
Instance
Object Name
ID
BV0
RUN/STOP ACT
BV1
FWD/REV ACT
BV2
FAULT ACT
BV3
EXT 1/2 ACT
BV4
HAND/AUTO ACT
BV5
ALARM ACT
BV6
MAINT REQ
BV7
DRIVE READY
BV8
AT SETPOINT
BV9
RUN ENA ACT
BV10
RUN/STOP CMD
BV11
FWD/REV CMD
BV12
RUN ENA CMD
BV13
EXT 1/2 CMD
BV14
FAULT RESET
BV15
MBOX READ
BV16
MBOX WRITE
BV17
LOCK PANEL
BV18
CTL OVERRIDE CMD
BV19
CTL OVERRIDE ACT
BV20
START ENABLE 1
BV21
START ENABLE 2
NOTE: For Present Value Access Types, R = Read-only,W = Writeable, C = Commandable .
Commandable values support priority arrays & relinquish defaults .
OM 1190-1 • MD4 VFD
Description
This object indicates the drive Run Status, regardless of the control source .
This object indicates the motor's rotation direction, regardless of the control source .
This object indicates the drive's fault status .
This object indicates which control source is active: External 1 or External 2 .
This object indicates whether the drive is under Hand or Auto control .
This object indicates the drive's alarm status .
This object indicates the drive's maintenance status . Refer to Group 29 in the drive's
parameter descriptions .
This object indicates whether the drive is ready to accept a run command .
This object indicates whether the drive is at the commanded setpoint .
This object indicates the Run Enable command status, regardless of the control source .
This object commands a drive start . Control requires either: Parameter 1001 value =
COMM for control by EXT1 or Parameter 1002 value = COMM for control by EXT2 .
This object commands a motor rotation direction change . Control requires 1003
= REQUEST and either: Parameter 1001 value = COMM for control by EXT1 or
Parameter 1002 value = COMM for control by EXT2 .
This object commands Run Enable . Control requires parameter 1601 value = COMM .
This object selects ext1 or ext2 as the active control source . Control requires parameter
1102 value = COMM .
This object resets a faulted drive . The command is rising-edge triggered . Control
requires parameter 1604 value = COMM .
This object reads a parameter (defined by AV25 MBOX PARAM) and returns it in AV26
MBOX DATA .
This object writes the data value specified by AV26, MBOX DATA, to a parameter
(defined by AV25, MBOX PARAM).
This object locks the panel and prevents parameter changes . The corresponding drive
parameter is 1602 .
This object commands the drive into BACnet Control Override . In this mode, BACnet
takes drive control from the normal source . However, the control panel's HAND mode
has priority over BACnet Control Override .
This object indicates whether the drive is in BACnet Control Override . (See BV18 .)
This object commands start enable1 . Control requires param 1608 value = COMM .
This object commands start enable1 . Control requires param 1609 value = COMM .
84
f
C
Ieldbus
onTrols
Present Value
Active/Inactive Text
Access Type
RUN/STOP
R
REV/FWD
R
FAULT/OK
R
EXT2/EXT1
R
HAND/AUTO
R
ALARM/OK
R
MAINT/OK
R
READY/NOT READY
R
YES/NO
R
ENABLE/DISABLE
R
RUN/STOP
C
REV/FWD
C
ENABLE/DISABLE
C
EXT2/EXT1
C
RESET/NO
C
READ/RESET
W
WRITE/RESET
W
LOCK/UNLOCK
W
ON/OFF
C
ON/OFF
R
ENABLE/DISABLE
C
ENABLE/DISABLE
C
www .DaikinApplied .com