Relay Output Control

Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
Table 53: Relay Output Control Protocol Reference
Drive Parameter
1401
RELAY OUTPUT 1
1402
RELAY OUTPUT 2
1
1403
RELAY OUTPUT 3
1
1410
RELAY OUTPUT 4
1
More than 1 relay requires the addition of a relay extension module
1
For example: To control relays 1 and 2 using serial communication:
Set parameters 1401 RELAY OUTPUT 1 and 1402 RELAY OUTPUT 1 = 35 (COMM) .
Then, for example using N2:
• To turn Relay 1 On: Force object B07 to On .
• To turn Relay 2 On: Force object B08 to On .
• To turn both Relay 1 and 2 On: Force objects B07 and B08 On .
NOTE: Relay status feedback occurs without configuration as
Table 54: Relay Status Feedback Protocol Reference
Drive Parameter
0122
RO 1-3 STATUS
0123
RO 4 STATUS
www .DaikinApplied .com
Value
Relay Output 1 controlled by
35 (COMM)
fieldbus.
Relay Output 2 controlled by
35 (COMM)
fieldbus.
Relay Output 3 controlled by
35 (COMM)
fieldbus.
Relay Output 4 controlled by
35 (COMM)
fieldbus.
Value
Relay 1...3 status .
Relay 4 status .
Setting
abb drv
40134 bit 0 or 00033
40134 bit 1 or 00034
40134 bit 2 or 00035
40134 bit 3 or 00036
defined below.
Setting
abb drv
40122
40123
77
f
Ieldbus
Protocol Reference
Modbus
1
N2
dcu profile
BO7
BO8
BO9
BO10
Protocol Reference
Modbus
N2
dcu profile
BI4...
0122
BI6
0123
BI7
OM 1190-1 • MD4 VFD
C
onTrols
FLN
BACnet
40
BO0
41
BO1
42
BO2
43
BO3
FLN
BACnet
BI0...
76... 78
BI2
79
BI3