Daikin ACS320 Operation Manual page 74

Wall or cabinet mountable drive for controlling ac motors
Table of Contents

Advertisement

Code
Description (continuation of Table 49)
5310
EFB PAR10 .
5311
EFB PAR11
5312
EFB PAR12
5313
EFB PAR13
5314
EFB PAR14
5315
EFB PAR15
5316
EFB PAR 16
5317
EFB PAR17
NOTE: After any changes to the communication settings, protocol must be reactivated by either cycling the drive power, or by
clearing and then restoring the station Id (5302) or use Reinitialize Device Service .
OM 1190-1 • MD4 VFD
Modbus
N2
Not used for Comm
Sets them response turnaround time in milliseconds . When this protocol is
setup
selected, the default value is:
3 msec .
Not used for Comm setup .
Not used for Comm setup .
Not used for Comm setup .
Not used for Comm setup .
Not used for Comm setup .
Not used for Comm setup .
74
EFB Protocol Reference
FLN
0 msec .
This parameter, together with
parameter 5317, EFB PAR 17,
sets BACnet Device Object
Instance IDs:
• For the range 1 to 65,535:
This parameter sets the ID
directly (5317 must be 0) . For
example, the following values
set the ID to 49134: 5311 =
49134 and 5317 = 0 .
• For IDs > 65,335: The ID
equals 5311's value plus
10,000 times 5317's value .
For example, the following
values set the ID to 71234:
5311 = 1234 and 5317 = 7 .
This parameter sets the BACnet
Device Object Max Info Frames
Property .
This parameter sets the BACnet
Device Object Max Master
Property .
This parameter indicates the
count of MS/TP tokens passed
to this drive .
This parameter works with
parameter 5311 to set BACnet
Device Object Instance IDs .
See parameter 5311 .
www .DaikinApplied .com
f
C
Ieldbus
onTrols
BACnet
5 msec .