Code Description (continuation of Table 27)
1104
REF1 MIN
Sets the minimum for external reference 1 .
• The minimum analog input signal (as a percent of the full signal in volts or amps) corresponds to REF1 MIN in Hz/rpm .
• Parameter 1301 MINIMUM AI1 or 1304 MINIMUM AI2 sets the minimum analog input signal .
• These parameters (reference and analog min . and max . settings) provide scale and offset adjustment for the reference .
1105
REF1 MAX
Sets the maximum for external reference 1 .
• The maximum analog input signal (as a percent of full the signal in volts or amps) corresponds to REF1 MAX in Hz/rpm .
• Parameter 1302 MAXIMUM AI1 or 1305 MAXIMUM AI2 sets the maximum analog input signal .
1106
REF2 SELECT
Selects the signal source for external reference REF2 .
0...17 – Same as for parameter 1103 REF1 SELECT .
19 = PID1OUT – The reference is taken from the PID1 output . See Groups 40 and 41 .