2
Overview
2.1.2
Mode of operation
Fig. 2.2
Typical installation position (as an example at the bus node CPX-FB33)
The MSE6-E2M is typically assembled behind a service unit combination.
It allows venting of the following system, both in the "Pressurise" state and in the "Shut-
off " state through a reverse flow (2 à 1). In the shut-off state, the reverse flow is consid
erably reduced. For this reason, for more rapid venting, the MSE6-E2M should be in the
"Pressurise" status.
The key functions are:
Standby detection and automatic shut-off of the compressed air supply
The MSE6-E2M uses settable parameters to detect production down times of a pneumatic system. The
system is separated from the compressed air supply using the 2/2 shut-off valve, without venting the
subsequent system. This avoids additional air consumption through leakages. If production is to con
tinue on the system, then it must be signaled to the MSE6-E2M. The shut-off valve opens and the sys
tem is again supplied with compressed air.
Automatic shut-off of the compressed air supply can be activated and deactivated by the user. In the
deactivated status, the shut-off valve can be controlled directly by the PLC.
Pressure tightness testing
When in the shut-off state, the MSE6-E2M measures the pressure curve over time.
Even in well-serviced systems, the pressure falls continuously due to leakages. The fewer leakages the
system has, the slower the pressure drop will be. The measured pressure change serves as a measure
of the leakage existing in the system. If the parameterised limit value is exceeded, then the device will
output a diagnostic message.
Pressure recording
The MSE6-E2M continuously measures the output pressure, prepares the data and makes it available
cyclically.
To detect high operating pressures, the MSE6-E2M offers the option of parameterising limit values for
pressure. If the parameterised limit value is exceeded, then the device will output a diagnostic mes
sage.
Festo – MSE6-E2M-IN-EN – 2017-07c – English
Machine/sys
tem
11