Operation; Maintenance; Maintenance Work; Cleaning - Festo MS6N-SV E-ASIS Series Assembly Installation Safety Instructions

Soft start/quick exhaust valve
Hide thumbs Also See for MS6N-SV E-ASIS Series:
Table of Contents

Advertisement

Operation

9
Operation
The mechanical system of the product is not tested when it is pressurised.
Perform a forced switch-off at least once a month if the process-related switching frequency is
lower.
When designing the system, take into account the maximum switching frequency and the life rating of
the product to ensure optimum availability è 14 Technical data.
10

Maintenance

10.1

Maintenance work

A dirty silencer can extend the time needed for exhausting the system and thus restrict the safety func-
tion.
Check the silencer regularly and replace if necessary.
10.2

Cleaning

1. Switch off energy sources:
Operating voltage
Compressed air
2. Clean the outside of the product as required. Approved cleaning agents are soap solutions (max.
+50 °C), petroleum ether and all non-abrasive cleaning agents.
11

Malfunctions

11.1

Diagnostics

LED display
LED AS-i
Diagnostics
Off
No AS-i voltage available
Illuminated green
AS-i interface voltage applied, no error
Illuminated red
AS-i address not set (equals 0)
Illuminated red
Failure of bus communication, e. g. watchdog expired
Flashes green/red
Error in exhaust valve
Tab. 10 Diagnostics LED AS-i
Festo — MS6(N)-SV-...-E-ASIS — 2019-05a