Overview
Flow recording
The MSE6-E2M continuously records the flow, prepares the data and makes it available cyclically.
To detect high flow rates, the MSE6-E2M offers the option of parameterising limit values for the flow. If
the parameterised limit value is exceeded, then the device will output a diagnostic message.
Consumption recording
The MSE6-E2M determines the compressed air consumption by recording the system flow rate. The
user has the option of using appropriate signaling to record the compressed air consumption over a
specific period of time.
2.2
Commissioning, diagnostics and operational functions
The system reaction of the MSE6-E2M can be adapted to the relevant application. The MSE6-E2M
provides extensive functions for commissioning, diagnosis and operation.
Commissioning and operational functions
The MSE6-E2M is supplied from the factory with preset parameters.
The behaviour of the MSE6-E2M can be adapted to the respective requirements through parameterisa
tion. The following behaviour can be influenced, for example, by accessing the internal parameters:
– The diagnostic behaviour by enabling maskable diagnostic messages
– Specification of the units and the measuring interval
– Setting of limit values
– The operating method of the diagnostic memory.
Caution
A different parameterisation will result in different characteristics.
In particular, check which settings are required when replacing the MSE6-E2M.
Ensure that the settings can be restored (e.g. in the start-up phase by the higher-or
der PLC/IPC).
Basic information on the different parameters can be found in Chapter 7. A detailed de
scription of the parameters can be found in Chapter 7 of the system description for the
energy efficiency module (è MSE6-E2M-SY-...).