COMM. Parameters
4.7.9
Function &
Default
COMM.Protocol
Modbus
Baud Rate
9600 (MODBUS)
Parity Check
EVEN
Station Number
OFF
S. Link Par. Set
Disabled
Ser. Link Control
Disabled
Store Settings
COMM. Parameters
Comm. Parameters
4.7.10
Function &
Default
COMM. PROTOCOL
Profibus
Baud Rate
AUTO (Profibus)
Parity Check
AUTO (Profibus)
PROFI.Network ID
OFF
S. Link Par. Set
Disabled
Ser. Link Control
Disabled
Store Settings
COMM. Parameters
Displays in MINIMIZED MODE and MAXIMIZED MODE.
42
42
– Page 8 – With the Modbus standard PCB
42
Range
Unit
Profibus/
Modbus/
DeviceNet
1200,
2400,
4800,
9600
EVEN,
ODD,
NO
OFF,1 –
247
Enabled/
Disabled
Enabled/
Disabled
– Page 8 – With the Profibus optional PCB
42
Range
Unit
Profibus/
Modbus/
DeviceNet
OFF, 1-126
Enabled/
Disabled
Enabled/
Disabled
Enabled/
Disabled
• Control Keypad
Sets ASTAT-XT's communication PROTOCOL.
Operational when the Modbus communication PCB is installed.
Sets ASTAT-XT's Baud Rate.
Sets ASTAT-XT's communication Parity Check.
Sets ASTAT-XT's communication Station Number.
Enables parameter modification via serial communication
Enables start, stop, reset, etc. via serial communication
Same as Store Settings Main Settings on page 28.
Note:
After changing communication parameters and storing them,
control power must be switched OFF and ON to load the new
communication parameters.
Sets ASTAT-XT's communication protocol.
Operational when the optional communication PCB is
installed.
User can not change the Baud Rate value.
Max. rate is 12 mega bit per second (MBPS).
User can not change the Parity Check value.
Sets the Profibus network ID.
When set to OFF the Profibus card will not function.
Enables parameter modification via serial
communication
Enables start, stop, reset, etc. via serial communication
Same as Store Settings Main Settings on
page 28.
Note:
After changing communication parameters and storing
them, control power must be switched OFF and ON to
load new communication parameters.