Standard Menu
The standard menu provides access to commonly used parameters, allowing the user to configure the
ASTAT XL as required for the application.
1
Motor Details
1A Motor Full Load Current
2
Primary Start/Stop
2A Start Mode
2B Current Limit
2C Initial Current
2D Start Ramp Time
2G Excess Start Time
2H Stop Mode
2I Stop Time
4
Protection Levels
4B Phase Sequence
4C Undercurrent
4D Instantaneous Overcurrent
4E Input A Trip
5
Protection Delays
5C Undercurrent Delay
5D Instantaneous Overcurrent Delay
5E Input A Trip Delay
5F Input A Initial Delay
6
Inputs
6D Input A Function
6E Input A Name
7
Relay Outputs
7A Relay A Function
7B Relay A On Delay
7C Relay A Off Delay
7D Relay B Function
7E Relay B On Delay
7F Relay B Off Delay
7G Relay C Function
7H Relay C On Delay
7I Relay C Off Delay
7J Low Current Flag
7K High Current Flag
7L Motor Temperature Flag
10
Display
10A Language
10B User Screen - Top Left
10C User Screen - Top Right
10D User Screen - Bottom Left
10E User Screen - Bottom Right
10J Display A or kW
38
ASTAT XL User Manual
DET-812
Fout! Stijl niet gedefinieerd.
Default Setting
Model dependent
Constant Current
350%
350%
00:10 mm:ss
00:20 mm:ss
Coast To Stop
00:00 mm:ss
Any Sequence
20% FLC
400% FLC
Always Active
00:05 mm:ss
00:00 mm:ss
00:00 mm:ss
00:00 mm:ss
Motor Set Select
Input Trip
Main Contactor
00:00 mm:ss
00:00 mm:ss
Run
00:00 mm:ss
00:00 mm:ss
Trip
00:00 mm:ss
00:00 mm:ss
50% FLC
100% FLC
80% FLC
English
Starter State
Blank
Hours Run
Blank
Current