Error Types - Siemens 2AI 2/4WIRE HF Manual

Table of Contents

Advertisement

Diagnostics

3.2 Error types

3.2
Error types
Analog input module error types
Table 3-1
16
D
9
D
7
D
8
D
6
D
16
Error types
Error type
10000: Parameter
assignment error
01001: Error
00111: Upper limit
exceeded
01000: Lower limit
value undershot
00110:
Open circuit
Meaning
Module cannot use the
parameter for the channel:
Inserted module does not
match the one configured.
Incorrect parameter
assignment.
Internal module error
(diagnostic message at
channel 0 applies to the entire
module)
Value is above the overshoot
range.
Value is below the underrange. Correct the module/final
Line to the encoder
interrupted.
2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0)
Remedy
Correct the configuration (align
actual and set configuration).
Correct the parameter
assignment (wire break
diagnostics only parameterized
for the permitted measuring
ranges).
Replace the module.
Correct the module/final
controlling element tuning.
controlling element tuning.
Correct the process wiring.
Manual, 04/2007, A5E01076111-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents