Table 50 continued: Unit Configuration Menu
Configuration
Description
Code Position
Return/Exhaust Fan Capacity
17
Control Method
18
Second Duct Pressure Sensor
19
Entering Fan Temp Sensor
20
Energy Recovery
21
Cooling Circuit Type
22
Head Pressure Control
23
Bypass Valve Control
24, 25, 26
Unit Size
27
Refrigerant Type
28
Reheat Type
29
Unit Voltage
30
EVType
Alarm Lists Menu
The Alarm Lists Menu is also available from the Service Menu
and is described on
page
62 .
www .DaikinApplied .com
Values (Default in Bold)
0=None
1=Tracking
2=Building Pressure
3=Speed
4=OADamper
0=No
1= Yes
0=No
1=Yes
0=None
1=ConstSpdWhl/NoRH
2=VarSpdWhl/Danfoss
3=VarSpdWhl/MD2
4=VarSpdWhl/MD3
5=VarSpdWhl/ABB
6=ConstSpdWhl/wRH
0=Individual
1=2,3 or 4 Circ . Water Condenser
Position 1 = 1 (SCU)
2=2 Circ . Air Condenser
0=No
1=Yes
Position 1 = 1 (SCU) .
0=Slave
1=Bypass
Position 1 = 1 (SCU) .
Three digits (default 050)
0=R22
1=R407C
2=R410A
0=None
1=StgHG
2=ModHG
3=StdHtRht
4=ModLSC
5=ModHG&LSC
0=208/60Hz
1=230/60Hz
2=460/60Hz
3=575/60Hz
4=208/50Hz
5=230/50Hz
6=460/50Hz
7=575/50Hz
0=None
1=EVB_Sag
2=EVB_DF
3=MTIII_Sag
4=MTIII_DF
5=MTIII_Sag_DF
6=MTIII_DF_Sag
73
Special Condition
RTU
●
●
●
●
Values 0 and 1
are valid only when
●
This position
is valid only when
This position
is valid only when
●
●
●
●
OM 920-6 • MICROTECH UNIT CONTROLLER