Advertisement

Alarm Delays Menu

The Alarm Delays Setup Menu can be accessed when a level 2
password has been entered . The default settings are the result
of many years of testing and should not be changed .
Table 35: Alarm Delays Setup Menu
Item Display Name
OffHtClDelay=
Frz DelayTime=
LP Delay=
LP Comp Delay=
Aflw Ignr Tm=
Sens Alm Dly=
Temp Alm Dly=
Emerg Stop=
OffHtClDelay is an adjustable item that is used to set the
duration the supply fan will remained energized when a unit
transitions to the off state while DX cooling or staged heating is
active .
Frz DelayTime is an adjustable item used to set the freeze
alarm delay time .
LP Delay is an adjustable item used to set the low pressure
switch delay time .
LP Comp Delay is an adjustable item used to set the low
pressure compressor delay time .
Aflw Ignr Tm is an adjustable item that sets the amount of
time the air proving switch is ignored after the supply fan is
started .
Sens Alm Dly is an adjustable item used to set the sensor
alarm delay time .
Temp Alm Dly is an adjustable item used to set the
temperature alarm delay time
Emerg Stop is an adjustable item used to set the emergency
shutdown to either manual or automatic restart .
OM 920-6 • MICROTECH UNIT CONTROLLER
Default Setting
120s
30s
2s
5s (410A)
65s (R22/407C)
120s
30s
30s
Alarm Config
Man Clr
58
Range
0–999s
0–180s
0–10s
0–300s
0–999s
0–300s
0–300s
Man Clr
Auto Clr
M
d
enu
esCrIpTIons
Password Level
2
2
2
2
2
2
2
2
www .DaikinApplied .com