Occupancy
Menus in the Occupancy menu contain status and control
items that relate to unit occupied/unoccupied operation .
Table 3: Occupancy Menu
Item Display Name
Occupancy=
Occ Mode=
OccSrc=
UnoccSrc=
Tnt Ovrde Time=
Occupancy is a status only item which indicates whether the
unit is currently in an occupied, unoccupied, or tenant override
mode of operation .
OccMode is an adjustable item which allows the unit to be
set for manual occupied or unoccupied operation, automatic
operation based on a time schedule input or manual tenant
override operation .
OccSrc is a status only item which indicates the input source
or function that is responsible for setting the Occupancy
parameter to "Occ" or "TntOvrd ."
www .DaikinApplied .com
Default Setting
Auto/Net
-
-
0
UnoccSrc is a status only item which indicates the input
source or function that is responsible for running the unit while
the Occupancy parameter to "Unocc ."
Tnt Ovrd Time is an adjustable item which indicates the
amount of time remaining for unit operation since tenant
override operation was activated .
25
Range
Occ
Unocc
TntOvrd
Occ
Unocc
TntOvrd
Auto/Net
None
NetSchd
IntSchd
OneEvnt
RemoteSw
OccManCmd
OccMode
TStatTO
ManTO
UnoccDehum
UnoccClg
UnoccHtg
IntOptStrt
NetOptStrt
None
0–300min
OM 920-6 • MICROTECH UNIT CONTROLLER