Heating Set-Up

The Heating menu provides a summary of the control
parameters for units with heating . The unit's heating mode
of operation is controlled by the control temperature and the
heating setpoint temperature . The unit goes into the heating
mode of operation by analyzing the control temperature .
Table 28: Heating Set-Up Menu
Item Display Name
Htg Stage Time
Htg DB
Htg Period=
Htg Gain=
Htg PAT=
Htg Max Chg
Htg Hi OAT Lock
OAT Diff
Htg Reset=
Min Htg Spt=
Min Htg Spt @
Max Htg Spt=
Max Htg Spt @
Min DAT Ctrl=
Min Dat Limit
F&BP Method=
F&BP ChgOvrT=
Occ Heating=
Unocc Diff=
Htg Warmup Tm=
Htg Hld Period=
Max Purge Hld=
Gas Derate V=
MWU Sensor
www .DaikinApplied .com
The control temperature can be return temperature, space
temperature or outside air temperature . The unit goes into the
heating mode of operation when the control temperature is
below the heating setpoint by more than ½ the deadband .
Default Setting
5min
2 .0°F
60s
0 .1
600s
10%
55°F
2°F
None
55 .0°F
0/NA
55 .0°F
100 .0°F
Yes
55 .0°F
OpenVlv
37°F
Yes
3°F
240s
240s
20s
10 .0V
RAT
49
Range
2–60min
1 .0–10 .0°F
0–999s
0 .0–100 .0
0–999s
0–100%
0–100°F
0–10°F
None
Ntwrk
Space
Return
OAT
ExtmA
ExtV
40 .0–140 .0°F
0–100/
NA
°F
°C
mA
40 .0–140 .0°F
0–100/
NA
°F
°C
mA
Yes, No
0 .0–70 .0°F
OpenVlv
ModVlv
0–60°F
Yes, No
0–10°F
0–999s
0–999s
10–180s
0–10 .0V
RAT
Space
None
OM 920-6 • MICROTECH UNIT CONTROLLER
M
d
enu
esCrIpTIons
Password Level
4
4
4
4
4
4
4
4
6
6
6
6
6
6
4
4
4
6
2
2
2
2
2
2