Rf/Ef Set-Up - Daikin MicroTech III Operation Manuals

For commercial rooftop, applied rooftop and self-contained systems
Hide thumbs Also See for MicroTech III:
Table of Contents

Advertisement

RF/EF Set-Up

Table 22: Return Fan/Exhaust Fan Set-up Menu
Item Display Name
RF/EF Ctrl=
Rem RAF Cap=
Rem ExhF Cap=
BSP DB=
BSP Period=
BSP Gain=
Max Spd Chg=
Sup Fan Max=
RF @ SF Max
Sup Fan Min=
RF @ SF Min=
Lo Fan Diff=
Hi Fan Diff=
RFEF Ctrl Dly=
Min Speed=
MinExStrtTime=
MinExStopTime=
MinExhOAPos=
MinExhSAFCap=
ExhOnOAPos=
ExhMxOAPos=
Exh Stg 1 On=
Exh Stg 1 Off=
Exh Stg 2 On=
Exh Stg 2 Off=
Exh Stg 3 On=
Exh Stg 3 Off=
Max RF/EF Hz=
Max RF/EF Hz=
Max RF/EF Hz=
MaxVentSpd=
Max RFEF RPM=
ECM Status=
OM 920-6 • MICROTECH UNIT CONTROLLER
Default Setting
Tracking
5%
5%
0 .01in
5s
0 .2
4%
100%
95%
30%
25%
75%
75%
30s
5% With Exhaust Fan
33% With Return Fan
120s
120s
5%
10%
40%
100%
40%
30%
55%
40%
70%
50%
60Hz
60Hz
60Hz
100%
2600
38
Range
None
Tracking
BldgP
Spd/Net
OA Damper
0-100%
0-100%
0 .0-0 .1in
0-999s
0 .0-100 .0s
0-100%
0-100%
0-100%
0-100%
0-100%
0-100%
0-100%
0-999s
0-100%
60-300s
60-300s
0-100%
0-100%
0-100%
0-100%
0-100%
0-100%
0-100%
0-100%
0-100%
0-100%
0-100Hz
0-100Hz
0-100Hz
0-100%
0-5000
OK
M
d
enu
esCrIpTIons
Password Level
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
N/A
N/A
N/A
2
2
2
www .DaikinApplied .com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents