Condenser Fan Control - Daikin MicroTech III Operation Manuals

For commercial rooftop, applied rooftop and self-contained systems
Hide thumbs Also See for MicroTech III:
Table of Contents

Advertisement

Condenser Fan Control

RPS Units
There are up to four condenser fans per circuit. The first fan on
each circuit is always turned on when any compressor on the
circuit is turned on through auxiliary switches on the compressor
contactors . The second two fans on each circuit (if applicable)
are controlled by outputs from the Main Controller . These are
controlled via Condenser Fan Output 1 and Condenser Fan
Output 2 . The last fan on each circuit (if applicable) is controlled
by an external refrigerant pressure switch .
Condenser Fan Output 1 is turned ON when any
compressor on is on and the OAT rises above the
Condenser Fan A Set Point . Condenser Fan Output 1 is
turned OFF when all compressors are OFF or the OAT drops
below the Condenser Fan 1 Set Point by more than the
Condenser Fan Differential (Default = 5°F) . External relays
allow operation of condenser fans associated with a specific
circuit only when a compressor on that circuit is ON .
The Condenser Fan default setpoints vary by unit size according to the following tables:
Table 55: 410A Condenser Fan Setpoints
CondFanOutput1
Unit
(MCB-DO7)
Size
Setpoint Differential Setpoint Differential Setpoint Differential
015
70
5
016
75
5
020
70
5
021
75
5
025
60
5
026
70
5
030
75
5
031
75
5
035
70
5
040
65
5
042
70
5
045
65
5
050
65
5
051
70
5
060
60
5
062
70
5
063
70
5
068
70
5
070
75
5
071
75
5
075
65
5
079
65
5
080
75
5
081
75
5
085
70
5
090
60
5
091
60
5
100
60
5
101
60
5
105
50
5
110
65
5
120
65
5
125
65
5
130
60
5
140
55
5
OM 920-6 • MICROTECH UNIT CONTROLLER
CondFanOutput2
PC13/PC231
(MCB-DO8)
90
90
85
5
90
80
5
90
90
90
90
85
5
90
85
5
90
85
5
90
85
5
90
80
5
90
90
5
90
85
5
90
85
5
90
85
5
90
80
5
90
Condenser Fan Output 2 is turned ON when any
compressor is ON and the OAT rises above the Condenser
Fan B Set Point . Condenser Fan Output 2 is turned OFF
when all compressors are OFF or the OAT drops below the
Condenser Fan 2 Set Point by more than the Condenser
Fan Differential (Default = 5°F) . External relays allow
operation of condenser fans associated with a specific
circuit only when a compressor on that circuit is ON .
Condenser Fan Output 3 is turned ON when any
compressor is ON and the OAT rises above the Condenser
Fan 3 Set Point . Condenser Fan Output 3 is turned OFF
when all compressors are OFF or the OAT drops below the
Condenser Fan 3 Set Point by more than the Condenser Fan
Differential (Default = 5°F) . External relays allow operation of
condenser fans associated with a specific circuit only when a
compressor on that circuit is ON .
Table 56: R22 Condenser Fan Setpoints
CondFanOutput1
Unit
(MCB-DO7)
Size
Setpoint Differential Setpoint Differential Setpoint Differential
015
60
018
60
020
60
025
65
030
65
036
70
040
65
045
65
050
60
060
25
070
40
075
65
080
65
090
65
105
0
Table 57: R407C Condenser Fan Setpoints
CondFanOutput1
35
Unit
(MCB-DO7)
Size
35
Setpoint Differential Setpoint Differential Setpoint Differential
35
015
60
35
018
0
35
020
0
35
025
65
35
030
65
35
036
65
35
040
60
35
045
55
35
050
50
35
060
15
35
070
30
35
075
65
35
080
65
35
090
50
35
105
0
126
o
peraTor
CondFanOutput2
CondFanOutput3
(MCB-DO8)
5
5
5
5
5
5
5
5
5
5
5
5
0
5
5
0
5
5
0
5
5
70
5
CondFanOutput2
CondFanOutput3
(MCB-DO8)
5
5
5
5
5
5
5
5
5
5
5
5
0
5
5
0
5
5
0
5
5
70
5
www .DaikinApplied .com
'
g
s
uIde
(MCB-DO6)
70
5
70
5
75
5
75
5
75
5
45
5
(MCB-DO6)
70
5
70
5
75
5
75
5
75
5
35
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents