Unit State is a status only item which indicates the state of
operation in which the unit is currently operating . The unit can
be in any of the operating states shown .
Unit Status is a status only item which indicates the status
of operation in which the unit is currently operating . The unit
status can be any of the status values shown .
MWU Status is a status only item that indicates whether or not
the unit is in the heating state due to MWU function .
Dehum Status is a status only item which indicates the status
of operation of the dehumidifier. The dehumidifier can be active
or inactive .
Ctrl Mode is an adjustable item which sets the operating mode
of the unit . The unit can be in any of the modes shown .
Occ Mode is an adjustable item which sets the occupancy
mode of the unit . The unit can be in occupied, unoccupied,
tenant override, or auto modes .
Clg Capacity is a status only item which indicates the
percentage of the unit maximum cooling capacity currently
operating .
OAD/Econo Cap is a status only item which indicates the
percentage that the outdoor damper or economizer valve is
currently open .
Htg Capacity is a status only item which indicates the
percentage of the unit maximum heating capacity currently
operating .
Reheat Capacity is a status only item which indicates the
percentage of the unit maximum reheat capacity currently
operating .
Control Temp is a status only item which displays the current
value of the "Control Temperature ." The "Control Temperature"
is defined as the temperature input selected by the Control
Temperature Source parameter . For example, if the Control
Temperature Source parameter is set to "Return," then the
control temperature parameter reads the same value as the
Return Air parameter .
Occ Clg Spt is a status only item which indicates the
temperature in which the unit will go into the cooling mode of
operation . Once a valid password has been entered this item
becomes an adjustable item.
Occ Htg Spt is a status only item which indicates the
temperature in which the unit will go into the heating mode of
operation . Once a valid password has been entered this item
becomes an adjustable item.
Disch Air is a status only item which displays the current
temperature reading from the unit's discharge air temperature
sensor (DAT) . This sensor is standard on all units .
DAT Clg Spt is a status only item which indicates the
temperature that the DAT should be maintained at when it is
in the cooling mode of operation . Once a valid password has
been entered this item becomes an adjustable item.
OM 920-6 • MICROTECH UNIT CONTROLLER
DAT Htg Spt is a status only item which indicates the
temperature that the DAT should be maintained at when in the
heating mode of operation . Once a valid password has been
entered this item becomes an adjustable item.
Min DAT Limit is a status only item which indicates the
discharge air low limit temperature on CAV zone control
units . Heating will be activated to maintain this setting when
the discharge temperature falls below it during the Fan Only
operating state . On VAV or CAV discharge control units, the
minimum discharge temperature limit is the DAT Clg Spt . Once
a valid password has been entered this item becomes an
adjustable item.
SAF Capacity is a status only item which indicates the
capacity of the supply air fan .
DSP is a status only item which displays the current duct static
pressure reading .
DuctSP Spt= is a status only item which indicates the duct
static pressure set point used for controlling the VFD for the
supply air fan . The VFD is modulated to maintain the duct
pressure at this value . Once a valid password has been
entered this item becomes an adjustable item.
RF/EF Capacity is a status only item indicating the capacity of
the return fan/exhaust air fans .
BSP is a status only item which displays the current building
static pressure reading .
BldgSP Spt is a status only item which indicates the building
static pressure set point used for controlling the return/exhaust
fan VFD . The return/exhaust fan VFD is modulated to maintain
the building static pressure sensor input to this value . Once
a valid password has been entered this item becomes an
adjustable item.
OA Temp is a status only item which displays the current
temperature reading from the unit mounted outdoor air
temperature sensor . This sensor is standard on all units .
EW Temp is a status only item that displays the current
temperature reading from the unit mounted entering water
temperature sensor . The sensor is standard on all water-cooled
units .
Rel Humidity is a status only item that displays the current
relative humidity reading from the optional humidity sensor .
22