Energy Recovery Set-Up - Daikin MicroTech III Operation Manuals

For commercial rooftop, applied rooftop and self-contained systems
Hide thumbs Also See for MicroTech III:
Table of Contents

Advertisement

Energy Recovery Set-up

The Energy Recovery Set-up menu contains parameters that
relate to or are used to control the enthalpy wheel and exhaust
fan when a unit is equipped with an optional energy recovery
wheel system .
Table 30: Energy Recovery
Item Display Name
Energy Rvcy=
ER Wheel=
Wheel Speed=
Whl Spd Cmd=
ER LAT=
ER EAT=
Min ExhT Diff=
Max ExhT Diff=
ER Whl Stg Tm=
ER Whl Off Tm=
Rel Humidity=
Min Whl Spd
Intersect Pt=
Fst Mgmt Meth=
OA Fst Temp=
Defrost Time=
Defrst Period=
Defrst On Tm=
Defrst Off Tm=
ER Whl Period=
ER Whl Gain=
ER Whl PAT=
ER Max Chg=
Capacity Limiting
www .DaikinApplied .com
Default Setting
Yes
2 .0°F
6 .0°F
5min
20min
5%
Timed
-20 .56°C
5min
60min
1s
24s
30 .0s
1 .0
30 .0s
10%
Yes
53
Range
Yes, No
On, Off
0–100%
0–100%
-50 .0–200 .0°F
–50 .0–200 .0°F
1 .0–20 .0°F
1 .0–20 .0°F
1–100min
1–100min
0–100%
0–100%
-146 .2 .0–150 .0°F
Timed ExhAir
-40 .0 – 37 .78°C
0–60min
0–1440min
0–999s
0–999s
0–999 .0s
0–100
0–999 .0s
0–100%
Yes
No
OM 920-6 • MICROTECH UNIT CONTROLLER
M
d
enu
esCrIpTIons
Password Level
4
4
4
4
4
4
4
4
4
4
4
4
2
4
4
4
4
2
2
2
2
2
2
2

Hide quick links: