Sensor Offsets Menu

The Sensor Offsets Menu provides a means of calibrating the
various temperature sensor inputs to the unit . Each sensor
can be "biased" by as much as +/- 10 .0°F .
Table 47: Sensor Offset Menu
Item Display Name
Disch Air=
Return Air=
SpaceTemp=
OA Temp=
ER LAT=
ER EAT=
DRT1=
DRT2=
OM 920-6 • MICROTECH UNIT CONTROLLER
Default Setting
0 .0°F
0 .0°F
0 .0°F
0 .0°F
0 .0°F
0 .0°F
0 .0°F
0 .0°F
68
Range
0 .0–10 .0°F
0 .0–10 .0°F
0 .0–10 .0°F
0 .0–10 .0°F
0 .0–10 .0°F
0 .0–10 .0°F
-10 .0–10 .0°C
-10 .0–10 .0°C
M
d
enu
esCrIpTIons
Password Level
2
2
2
2
2
2
2
2
www .DaikinApplied .com