Quick Menu
Items in the Quick Menu contain basic unit operating status
and control set point parameters . The items shown in the Quick
Menu are Read Only if a valid password has not been entered .
The following are brief descriptions of the Quick Menu items .
No password is required to view the Quick Menu .
Table 1: Quick Menu
Menu Display Name
Unit State=
Unit Status=
MWU Status=
Dehum Status=
Ctrl Mode=
Occ Mode=
Clg Capacity=
OAD/Econo Cap=
Htg Capacity=
Reheat Capacity=
Control Temp=
Occ Clg Spt =
Occ Htg Spt =
Disch Air=
DAT Clg Spt=
DAT Htg Spt=
Min DAT Limit=
SAF Capacity=
DSP
DuctSP Spt=
RF/EF Capacity=
BSP=
BldgSP Spt=
OA Temp=
EW Temp=
Rel Humidity=
www .DaikinApplied .com
Default Setting
—
—
—
—
Off
Auto/Net
—
—
—
—
—
72 .0°F
68 .0°F
—
55 .0°F
85 .0°F
55 .0°F
—
—
1 .0 in
—
—
0 .050 in
—
—
—
21
Range
Off
Start
Recirc
FanOnly
MinDAT
Htg
Econo
Clg
Enable
OffMan
OffMnCtl
OffNet
OffAlm
OffFnRty
Inactive
Active
Active/Inactive
Off
HeatOnly
CoolOnly
FanOnly
HeatCool
Auto/Net
Occ
Unocc
TntOvrd
Auto/Net
0–100%
0–100%
0–100%
0–100%
-50 .0–200 .0°F
0 .0–100 .0°F
0 .0–100 .0°F
-50 .0–250 .0°F
40 .0–100 .0°F
40 .0–140 .0°F
0 .0–70 .0°F
0–100%
0 .2–4 .0 in
0 .2–4 .0 in
0–100%
-0 .25–0 .25 in
-0 .25–0 .25 in
-50 .0–200 .0°F
-50 .0–150 .0°F
0–100%
OM 920-6 • MICROTECH UNIT CONTROLLER
M
d
enu
esCrIpTIons
M
d
enu
esCrIpTIons
Password Level
None
6
6
6
6
6
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None