Dehum Set-Up

Table 29: Dehumidification Menu
Item Display Name
Dehum Method=
RH DB=
Dewpoint DB=
RH Period=
RH Gain=
RH PAT=
RH Max Chg=
LSC Lo Gain=
RH Stg Time=
Stg Rht DB=
Dehum Ctrl=
Sensor Loc=
Mn Lvg Coil T=
Mx Lvg Coil T=
Rht Cmp Lmtg=
Min Rheat Spt=
Max Rheat Spt =
RH Sens Type=
RH Min Sig=
RH Max Sig=
Min Dehum Spd=
Max Dehum Spd=
Rht Min Pos=
RH Dec Rate=
www .DaikinApplied .com
Default Setting
None
2%
2 .0°F
30s
1
30s
10%
0 .2
10min
5°F
Occupied
Return
45 .0°F
52 .0°F
Yes
55 .0°F
65 .0°F
VDC
0 .0V
10 .0V
33%
100%
10% (RPS)
15% (MPS, DPS, DPH)
1
51
Range
None
Rel Hum
DewPt
Always
0–10%
2–10°F
0–999s
0 .0–100 .0
0–999s
0–100%
0 .0–100 .0
0–60min
0–20°F
Occupied
Always
Return
OAT
Space
40–100°F
40–100°F
No
Yes
40 .0–100 .0°F
40 .0–100 .0°F
VDC
mA
0 .0–20 .0
V/mA
0 .0–20 .0
V/mA
0–100%
0–100%
0–100%
0–10 .00%/s
OM 920-6 • MICROTECH UNIT CONTROLLER
M
d
enu
esCrIpTIons
Password Level
4
4
4
4
4
4
4
2
4
4
4
4
4
4
2
4
4
2
2
2
2
2
2
2

Hide quick links: