Daikin MicroTech III Operation Manuals page 32

For commercial rooftop, applied rooftop and self-contained systems
Hide thumbs Also See for MicroTech III:
Table of Contents

Advertisement

One Event Schedule Menu
The One Event Schedule is used to set the start and stop times for one event .
Table 16: One Event Schedule Menu
Item Display Name
Beg=
End=
Optimal Start Menu
The Optimal Start menu is used to set up the unit so it starts at the most efficient time before building occupancy.
Table 17: Optimal Start Menu
Item Display Name
Enable=
Htg Rate=
Htg OAT=
Des Htg OAT=
Clg Rate=
Clg OAT=
Des Clg OAT=
Enable is an adjustable item that turns on the optimal start
feature . Setting the value to yes will activate this function .
Htg Rate is an adjustable item used by the controller in
determining the amount time before occupancy to start when
the Optimal Start parameter is set to "ON ."
Htg OAT is an adjustable item used by the controller in
determining the amount time before occupancy to start when
the Optimal Start parameter is set to "ON ."
Design Htg OAT is an adjustable item that sets the outdoor
air temperature at which the heating system could just hold the
load . The rate of temperature rise would equal zero .
Daylight Savings Menu
Table 18: Daylight Savings Menu
Item Display Name
DLS Strt Mon=
DLS Strt Wk=
DLS End Mon=
DLS End Week=
DLS Enable=
DLS Strt Mon is an adjustable item that sets the month for
daylight savings time to begin .
DLS Strt Wk is an adjustable item that sets the week of the
month for daylight savings time to begin .
DLS End Mon is an adjustable item that sets the month for
daylight savings time to end .
OM 920-6 • MICROTECH UNIT CONTROLLER
Default Setting
MMMDD/99 @ HH:MM
MMMDD/99 @ HH:MM
Default Setting
No
0 .4°F/min
35°F
0°F
0 .4°F/min
85°F
95°F
Default Setting
Mar
2ndWeek
Nov
1stWeek
Auto
32
Range
00/00/00-12/31/99 @ 00:00 – 23:59
00/00/00-12/31/99 @ 00:00 – 23:59
Range
No, Yes
0 .0–1 .0°F/min
-40–60°F
-40–60°F
0 .0–1 .0°F/min
-60–140°F
-60–140°F
Clg Rate is an adjustable item that sets the rate of temperature
drop in degrees per minute when the unit last started optimally
in cooling .
Clg OAT is an adjustable item that sets the outdoor air
temperature when the unit was last started optimally in cooling .
Design Clg OAT is an adjustable item that sets the outdoor
air temperature at which the cooling system could just hold the
load . Rate of temperature rise would equal zero .
Range
NA
Jan-Dec
1stSun
2ndSun
3rdSun
4thSun
5thSun
NA
Jan-Dec
1stSun
2ndSun
3rdSun
4thSun
5thSun
Off/Auto
DLS End Week is an adjustable item that sets the week of the
month for daylight savings time to end .
DLS Enable is an adjustable item that sets whether or not
daylight savings time is enabled .
M
d
enu
esCrIpTIons
Password Level
6
6
Password Level
6
2
2
2
2
2
2
Password Level
2
2
2
2
2
www .DaikinApplied .com