Parameter Range And Define; Parameters Table (Table 1) - Smartgen HGM6000K Series Operating Manual

Automatic generator module
Table of Contents

Advertisement

Pin
Function
40
Common port
Note:
1. These terminals of 31, 32, 33, and 34 are not used for HGM6010KC
module.
2. Back LINK interface as a parameter programming interface, used by SG72
adapter PC controller programming.

7 PARAMETER RANGE AND DEFINE

All parameters of HGM6000K series as follows:
Note: small brackets set item number 6010KC.

7.1 PARAMETERS TABLE (TABLE 1)

Num
Parameter
Mains
P 01
normal delay
Mains volt
P 02
abnormal
delay
Mains
under
P 03
volt
Mains
P 04
volt
Transfer
P 05
switch interval
P 06
Start delay
(P01)
P 07
Stop delay
(P02)
HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module
Dim
1.0mm Auxiliary input common port
Range
volt
(0-3600)s
(0-3600)s
(30-360)V
over
(30-360)V
(0-99.9)s
(0-3600)s
(0-3600)s
Description
Default
10
Mains
suited for ATS(automatic
transfer switch)
5
When
under than the point, mains
under voltage are active.
184
When the point is zero,
mains under voltage are
disabled.
When mains voltage is over
than the point, mains over
276
voltage are active. When
the point is 360V, mains
over voltage are disabled.
It‟s the delay from mains is
opened to genset closing or
1.0
from genset is opened to
mains closing.
It‟s the delay from remote
start signal is active or
1
mains is failure, to start
genset.
It‟s the delay from remote
start signal is inactive or
1
mains is normal, to stop
genset.
ISSUE 2011-06-20
Version 1.7
Remark
transient
delay,
mains
voltage
is
Page 17 of 34