Configurable Parameters; Configurable Parameters Table - Smartgen HGM501 User Manual

Genset controller
Hide thumbs Also See for HGM501:
Table of Contents

Advertisement

Terminal
10
Electric Lock START Input
11
Start Relay Output
12
Fuel Relay Output
13
Fuel/Start Relay Common Port
NOTE: Controller within the LINK port, which connect to SmartGen's SG72 adapter. It is can be set or
check genset's real time data via PC software.
7.

CONFIGURABLE PARAMETERS

7.1. CONFIGURABLE PARAMETERS TABLE

No
Parameter
1
AC system
2
Rated voltage
Rated
3
frequency
4
Rated power
Enable
5
protection
6
CT Ratio
Engine
7
temperature
sensor type
HGM501 Genset Controller User Manual
Function
Table 5 – Configurable Parameters
Range
1P
2P
3P
4P
110 V
115 V
120 V
130 V
220 V
230 V
240V
50Hz
60Hz
(0.0-99.9)kw
Auto
Enable
Disable
(0-999)/62.5
L-0
L-1
L-2
L-3
L-4
Wire size
Hand-turn start, start relay output
(Output activates when electric
1.5mm
2
lock key is turned to START
position)
Rated current 7A; power supplied
1.5mm
2
by terminal 13
Rated current 7A; power supplied
1.5mm
2
by terminal 13
Fused and connected to start
2.5mm
2
battery positive
Default
1P:1P2W
2P:2P3W
1P
3P:3P4W
4P:Double Rated Volts
Generator rated voltage value
220
selection
Generator
50
selection
5.0
Generator rated Active power
Irrespective of whether gen-set
Enable
auto protection is enabled
Unit: A/62.5mA
50/62.5
(Must correspond to the used
current transformer)
L-0:Not used
L-1:TE1(SGX Sensor)
L-4
L-2:TE2(SGD Sensor)
L-3:TE3(PT100 Sensor)
L-4:TE4 (See TE4/TG4 Sensor
Remarks
Description
rated
frequency
Page 11 of 17

Advertisement

Table of Contents
loading

Table of Contents