Parameters List; Table 16: Input Selector Block Parameters - Honeywell SLG 700 Option Manual

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Parameters List

Table 17: Input Selector block parameters
Parameter
ST_REV
The revision level of the static data associated with the function block.
The revision value increments each time a static parameter value in the
block is changed.
TAG_DESC
The user description of the application of the block.
STRATEGY
Used to identify grouping of blocks. This data is not checked or processed
by the block.
ALERT_KEY
The identification number of the plant unit. This information may be used
in the host for sorting alarms, etc.
MODE_BLK
The Actual, Target, Permitted, and Normal modes of the block.
Target: The mode to "go to".
Actual: The mode the "block is currently in".
Permitted: Allowed modes that target may take on.
Normal: Most common mode for target.
BLOCK_ERR
This parameter reflects the error status associated with the hardware or
software components associated with a block. It is a bit string, so that
multiple errors may be shown.
OUT
The block output value and status.
GRANT_DENY
Options for controlling access of host computers and local control panels
to operating, tuning, and alarm parameters of the block. Not used by
device.
STATUS_OPTI
It helps to select options for status handling and processing. The
supported status option for the integrator block is: "Use Uncertain as
ONS
Good", "Uncertain if MAN mode."
IN_1
The block input value and status.
IN_2
The block input value and status.
IN_3
The block input value and status.
IN_4
The block input value and status.
DISABLE_1
Parameter to switch off the input from being used. 0 - On, 1 - Off.
DISABLE_2
Parameter to switch off the input from being used. 0 - On, 1 - Off.
DISABLE_3
Parameter to switch off the input from being used. 0 - On, 1 - Off.
DISABLE_4
Parameter to switch off the input from being used. 0 - On, 1 - Off.
SELECT_TYPE
Determines the selector action: First Good, Minimum, Maximum, Middle,
and Average.
The minimum number of inputs which are "Good" is less than the value of
MIN_GOOD
MIN_GOOD then set the OUT status to "Bad".
SELECTED
The integer indicating the selected input number.
OP_SELECT
An operator settable parameter to force a given input to be used.
Page 88
FOUNDATION Fieldbus Option User's Manual
Description
Rev.5