Sensor Connection Type:
Read-only parameter indicating how the Sensor Housing and Process Connector are connected
together. In most cases these two components are connected end-to-end in the Direct mount mode. For
harsh environments where the temperature at the Process Connector is too high for the electronics
inside the Sensor Housing, a 3m Remote Mount cable is available to physically separate the electronics
from the process connector. When the Remote mount mode is used, the transmitter will acquire a
longer echo curve to cover the additional length of the Remote Mount cable, and will use the process
connector reflection as the datum point to find the transmitter's Reference Plane location.
Mounting Location:
This parameter allows users to select the option that best describes how the GWR transmitter is located
on the tank. The available selections are:
Tank (Mounted to a flat surface in the tank ceiling or wall)
Bracket (Mounted to a bracket over an open roof tank)
Nozzle (See transmitter specifications for limits on nozzle dimensions)
Bypass (See transmitter specifications for limits on bypass dimensions)
Stillwell (Stillwell must extend beyond the length of the probe)
Unknown (To be used only if none of the above are applicable)
Selecting the Bypass or Stillwell options require an additional parameter entry to specify the inside
diameter of the bypass or stillwell. Selecting the Nozzle option requires two additional parameter
entries to specify both the inside diameter and length of the nozzle.
Mounting Angle:
The physical angle at which the probe is mounted relative to vertical (0 degrees means the probe is
perfectly vertical).
Mounting Height:
It is the length of the nozzle/Bypass pipe from the transmitter reference plane to the bottom of
the Nozzle.
Mounting Diameter:
It is the inner diameter of the Nozzle/Bypass.