6.6.2.6 Probe
Probe Type:
Only adjust this if you are changing the type of probe. Adjustments to the
calibration offsets and many other tuning parameters may be necessary if
the probe is changed. The available options are: Custom, Rod, Wire,
Multi-Twist Wire and Coax. (Single-twist wire requires a selection of
wire and Multi-twist wire requires a selection of multi-twist wire).
Probe Material:
Probe Material provides user an option to select the material with which
probe is made of.
Probe Diameter:
Probe Diameter can be selected from the options available via drop down.
Probe End Type:
This parameter specifies how the probe is terminated. For Rod and
Coaxial probes the only available option is None. For Wire probes the
available options are Clamp, Weight and Loop.
Probe Length:
This is a factory setting based on the purchase order. Adjustments to this parameter is only required if
the probe has been replaced or cut shorter. This parameter should always be measured from the
reference plane to the effective end of the probe. For a Coaxial probe and a Rod probe without a
centering disk, the effective end of the probe is
the physical end of the probe. For a Rod probe with a centering disk attached, the effective end of the
probe is the top surface of the centering disk. For a Wire probe with an end weight, the effective end of
the probe is the top of the end weight.