Parameter Name
VOL_CAL_TYPE
Page 50
FOUNDATION Fieldbus Option User's Manual
Description
Calculation method for Volume calculation
1.
Strapping Table
2.
Ideal Tank Shape
Note 1: The Strapping Table can be selected only when
the Volume Strapping Table size, Level and Volume
tables are valid. The strapping size should not be zero
and the level & volume tables should be in proper order
to select the Strapping Table option.
The Ideal Tank Shape can be selected and the relevant
tank configurations can be updated.
Note 2: Select Volume Calculation Type as None if
Volume related device variables (Product Volume) are
not required to be measured and monitored by device.
Note 3: The SLG 700 directly measures only distance
and related quantities (level, percent of range, etc.). The
calculation of volume is based on measured level and
additional tank geometry measurements. Reliable
volume calculation requires correct measurements of
tank geometry.