INTEG_OPTS: 0 (Flow reverse)
When this option is selected, only reverse flows is considered for integration. If there is no reverse
flow inputs (whose value is negative), and if one inputs is forward (whose value is positive) the
integration continues.
Note:
If both the inputs are forward, then the integration stops.
INTEG_OPTS: 0 (Use uncertain)
When this option is selected, the input (IN_1/IN_2) whose status is Uncertain is considered for
integration.
INTEG_OPTS: 0 (Use Bad)
When this option is selected, the input (IN_1/IN_2) whose status is Bad is considered for integration.
INTEG_OPTS: 0 (Carry)
This option is used only for UP_AUTO and DN_AUTO kind of integrations only. When this option is
selected, the residual value after the integration is added / subtracted from the integral value in the next
cycle of integration.
INTEG_OPTS: 0 (Add Zero if Bad)
When this option is selected, if IN_1/IN_2 is bad, the input value is zero for that input and integration
does not happen. Integration stops at the last value.
INTEG_OPTS: 0 (Confirm reset)
This option is to be selected in conjunction with RESET_CONFIRM.VALUE. When the value of
RESET_CONFIRM.VALUE is 1, and "Confirm Reset" is selected, the block gets reset. This is not
applicable to UP_AUTO and DN_AUTO types.
Rev.5
FOUNDATION Fieldbus Option User's Manual
Page 95