Maximum Filling Rate:
This parameter indicates the maximum rate at which the tank is expected to be filled or emptied. This
allows the transmitter to collect data over the correct area of the probe so that the surface and/or
interface positions can be tracked effectively and aids in the rejection of false reflections that might
look similar to the correct reflections. The valid range is between 0.04-0.2m/s (0.1312-0.656ft/s). The
sensor uses this value to discard erroneous echoes. It is recommended that a value somewhat larger
than that
6.6.2.7 Mounting
The main configuration parameters in this group deal with describing how the transmitter is physically
mounted to the tank. The lower portion of the display provides access to a number of advanced options
and actions that may be necessary to fine tune the transmitter performance in cases where the
characteristics of the mounting cause disturbances that cannot be modeled in the factory.
Transmitter Model:
Read-only parameter reflecting the model of transmitter ordered, either SLG720 or SLG726.
Process Connector Type:
Read-only parameter indicating whether the transmitter was order with a flange for mounting to the
tank or with a simple threaded connection.